Service & Parts Manual (2019, 2020, 2021, 2022)
Table Of Contents
50 PB
COMPONENT TESTING
Compressor Replacement -Special Procedure in Case of Compressor Burnout
WARNING
HIGH PRESSURE HAZARD 
Sealed Refrigeration System contains refrigerant 
and oil under high pressure.
Proper safety procedures must be followed, 
and proper protective clothing must be worn 
when working with refrigerants.
Failure to follow these procedures could 
result in serious injury or death. 
WARNING
ELECTRIC SHOCK HAZARD 
Turn  off  electric  power  before  service  or 
installation.  Extreme  care  must  be  used,  if  it 
becomes necessary to work on equipment with 
power applied.
Failure to do so could result in serious injury or 
death.
WARNING
EXPLOSION HAZARD 
The use of nitrogen requires a pressure
regulator. Follow all safety procedures and 
wear protective safety clothing etc. 
Failure to follow proper safety procedures 
could result in serious injury or death. 
1. Recover all refrigerant and oil from the system. 
2. Remove compressor, capillary tube and lter drier from the 
system. 
3. Flush evaporator condenser and all connecting tubing with dry 
nitrogen or equivalent. Use approved ushing agent to remove all 
contamination from system. Inspect suction and discharge line for 
carbon deposits. Remove and clean if necessary. Ensure all acid is 
neutralized. 
4. Reassemble the system, including new drier strainer and capillary 
tube. 
5. Pressurize with a combination of R-410A and nitrogen and leak test 
all connections with a leak detector. Recover refrigerant and repair 
any leaks found.
5a. If leak detector is unavailable remove all refrigerant from system 
and pressurize with nitrogen to 550 psi. Check that system holds 
pressure.
Repeat Step 5 to insure no more leaks are present
6. Evacuate the system with a good vacuum pump capable of a nal 
vacuum of 500 microns or less. The system should be evacuated 
through both liquid line and suction line gauge ports. While the unit 
is being evacuated, seal all openings on the defective compressor. 
Compressor manufacturers will void warranties on units received not 
properly sealed. Do not distort the manufacturers tube connections.
7. Recharge the system with the correct amount of refrigerant. The 
proper refrigerant charge will be found on the unit rating plate. The 
use of an accurate measuring device, such as a charging cylinder, 
electronic scales or similar device is necessary.
ROTARY AND SCROLL COMPRESSOR SPECIAL TROUBLESHOOTING 
AND SERVICE 
Troubleshooting and servicing rotary compres-sors is basically 
the same as on the reciprocating compressor with only one main 
exception: 
NEVER, under any circumstances, liquid charge a rotary-compressor 
through the LOW side. Doing so would cause permanent damage to 
the new compressor. Use a charging adapter.