Service & Parts Manual (2019, 2020, 2021, 2022)
Table Of Contents
52 PB
COMPONENTS TESTING
Heating Element
WARNING
ELECTRIC SHOCK HAZARD 
Turn  off  electric  power  before  service  or 
installation.  Extreme  care  must  be  used,  if  it 
becomes necessary to work on equipment with 
power applied.
Failure to do so could result in serious injury or 
death.
Heating Element 
Example
Electric heat models are equipped with a heating element 
The KEQ08A11A Model is equipped with a 1.15 kw(@115 Volts) Heating Element.
The heating element contains a fuse link and a heater limit  switch. The fuse link is in series with the power supply and will 
open and interrupt the power when the temperature reaches 199°F or a short circuit occurs in the heating element. Once the 
fuse link separates, a new heater element must be installed. 
NOTE: Always replace heating element with the exact replacement. 
The heater element has a high limit control. This control is a bimetal thermostat mounted in the top of the heating element. 
Should the fan motor fail or lter become clogged, the high  limit control will open and interrupt power to the heater before  
reaching an unsafe temperature condition. 
The control is designed to open at 110°F ±6°F. Test continuity  below 110°F or when it is cooled off. 
TESTING THE HEATING ELEMENT
Testing of the elements can be made with an ohmmeter across the terminals after the connecting wires have been removed. 
A cold resistance reading of approximately 10.11 ohms for the 1.15 KW heater should be registered. 
Drain Pan Valve 
During the cooling mode of operation, condensate which collects in the drain pan is picked up by the con-denser fan blade and 
sprayed onto the condenser coil. This assists in cooling the refrigerant plus evaporating the water. 
During the heating mode of operation, it is necessary that water be removed to prevent it from freezing during cold outside 
temperatures. This could cause the con-denser fan blade to freeze in the accumulated water and prevent it from turning.  
To provide a means of draining this water, a bellows type drain valve is installed over a drain opening in the base pan. 
This valve is temperature sensitive and will open when the outside temperature reaches 40°F. The valve will close gradually as 
the temperature rises above 40°F to fully close at 60°F. 
DRAIN PAN VALVE  
During the cooling mode of operation, condensate which collects in the drain pan is picked up by the con-denser fan blade and 
sprayed onto the condenser coil. This assists in cooling the refrigerant plus evaporating the water. 
During the heating mode of operation, it is necessary that 
water be removed to prevent it from freezing during cold 
outside temperatures. This could cause the con-denser fan 
blade to freeze in the accumulated water and prevent it from 
turning. 
To provide a means of draining this water, a bellows type 
drain valve is installed over a drain opening in the base pan. 
This valve is temperature sensitive and will open when the 
outside temperature reaches 40°F. The valve will close 
gradually as the temperature rises above 40°F to fully close 
at 60°F. 
Bellows Assembly 
Drain Pan Valve 
Figure 704 (Heating Element)
Figure 705 Drain Pan Valve