Service & Parts Manual (2019, 2020, 2021, 2022)
Table Of Contents
58 PB
FAULT 
CODE
PROBLEM CONTROL BOARD'S ACTION
1 Front Panel Button Stuck For More 
Than 20 Seconds
Continue to monitor for "OPEN" (Unstuck) switch. Do not process 
switch input. ENSURE FRONT COVER DOES NOT DEPRESS 
BUTTONS
3 Indoor Temperature Sensor is Open 
or Shorted
Set temp to 75°F in COOLING or 68°F in HEATING. Unit continues 
to operate
4 Indoor Coil Temperature Sensor is 
Open or Shorted
Control Board sets temp to a default of 40°F. Override sensor. 
Unit continues to operate.
5 Outdoor Coil Temperature Sensor is 
Open or Shorted
Sets temp to 20°F. Override sensor. Continue operation. Use Elec 
Heat if available for HEATING. If not available use HEAT PUMP if 
outdoor temp allows.
6 Outdoor Coil > (greater than) 175 F Shut down for 5 min. 
7 Indoor Coil < (less than) 30 F for 2 
consecutive minutes
Turn compressor off. When coil temp reachs 45°F resume 
operation after lockout time.
8 Unit Cycles > (grater than) 9 Times 
per hour
Continue operation. Continue to monitor. Take no action. Log 
Only.
9 Unit Cycles < (less than) 3 Times per 
Hour
Continue operation. Continue to monitor. Take no action. Log 
Only.
12 Discharge Air > (greater than) 185 F Shutdown electric heater until temp is 100°F.  Resume 
operation.
14 Discharge Air Temperature Sensor 
is Open or Shorted
Override Sensor. Set temp to 75°F. Continue to monitor. Set 
error code 14 ON.
16 Temperature Beyond Operating 
Limits
Ambient temp < (less than) 0°F and ambient temp > (greater 
than) 130°F.  Set error code 16 ON. When cleared return unit to 
normal.
22  Outdoor Coil Temperature < 30 F 
for 2 consecutive Minutes 
Unit will use electric heat to satisfy heating demands until temp 
is greater than 45°F. Unit must be a Heat Pump with electric 
heat.
23 Frost Protection. Unit will run active defrost for up to 6 minutes when Heat Pump 
run time is greater than 60 minutes and outdoor coil temp is 26 F 
or less. 
TROUBLESHOOTING
Diagnostic Codes
Figure 710 (Fault Codes)