Service & Parts Manual (Non Q) (2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- SPECIFICATIONS
- OPERATION
- ROUTINE MAINTENANCE
- REMOVE AND INSTALL THE CHASSIS
- R-410A SEALED SYSTEM REPAIR
- COMPONENT TESTING- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Replace The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement
- Fan Motor
- Capacitors
- Heating Element
- Drain Pan Valve
- Testing the User Interface and Electronic Control Board
- Thermistors Description
- Electronic Control Board Identification
- Replace the Electronic Control Board
- Replace the User Interface
 
- TROUBLESHOOTING
- WIRING DIAGRAMS
- PARTS CATALOG
- Available Accessories
71 PB
Problem Possible Cause Possible Solution
Unit does not operate.
The power button is off or the set point tem-
perature is satised.
Push the power button on and raise or lower 
temperature setting (as appropriate) to call for 
operation.
The LCDI power cord is unplugged.
Plug into a properly grounded 3 prong receptacle. 
(See Electrical Rating Tables, Figure 206) for the 
proper receptacle type for your unit.
The LCDI power cord has tripped (Reset 
button has popped out).
Press and release RESET (Listen for click. Reset 
button latches and remains in.) to resume operation.
The circuit breaker has tripped or the sup-
ply circuit fuse has blown.
Reset the circuit breaker, or replace the fuse as 
applicable. If the problem continues, contact a 
licensed electrician.
There has been a local power failure.
The unit will resume normal operation once power 
has been restored.
Unit Trips Circuit Breaker or  
Blows Fuses.
Other appliances are being used on the 
same circuit. (115 Volt only)
The unit requires a dedicated outlet circuit, not 
shared with other appliances.
An extension cord is being used.
Do NOT use an extension cord with this or any other 
air conditioner.
The circuit breaker or time-delay fuse is not 
of the proper rating.
Replace with a circuit breaker or time-delay fuse of 
the proper rating. (See Electrical Rating Tables, Fig-
ure 206) for the proper circuit breaker/ fuse rating for 
your unit. If the problem continues, contact a licensed 
electrician.
LCDI Power Cord Trips  
(Reset Button Pops Out).
The LCDI power cord can trip (Reset but-
ton pops out) due to disturbances on your 
power supply line.
Press and release RESET (Listen for click. Reset 
button latches and remains in.) to resume normal 
operation.
Electrical overload, overheating, or cord 
pinching can trip (Reset button pops out) 
the LCDI power cord.
Once the problem has been determined and cor-
rected, press and release RESET (Listen for click. 
Reset button latches and remains in.) to resume 
normal operation.
NOTE:  A damaged power supply cord must be replaced with a new power supply cord obtained 
from the product manufacturer and must not be repaired.
Unit Does Not Cool/ Heat Room 
Sufciently, or Cycles On And Off 
Too Frequently.
•  The return/ discharge air grille is 
blocked.
•  Ensure that the return and/ or discharge air 
paths are not blocked by curtains, blinds, furni-
ture, etc.
•  Windows or doors to the outside are 
open.
•  Ensure that all windows and doors are closed.
•  The temperature is not set at a cool 
enough/ warm enough setting.
•  Adjust the Temperature control to a cooler or 
warmer setting as necessary.
•  The lter is dirty or obstructed.
•  Clean the lter, (see Routine Maintenance), or 
remove obstruction.
•  The indoor coil or outdoor coil is dirty 
or obstructed.
•  Clean the coils, (see Routine Maintenance), or 
remove obstruction.
•  There is excessive heat or moisture 
(cooking, showers, etc.) in the room.
•  Be sure to use exhaust vent fans while cooking 
or bathing and, if possible, try not to use heat 
producing appliances during the hottest part of 
the day.
•  The temperature of the room you are 
trying to cool is extremely hot.
•  Allow additional time for the air conditioner to 
cool off a very hot room.
TROUBLESHOOTING 
Troubleshooting Tips
Figure 717 (Troubleshooting Tips)










