4.1 E.S.P. (External Static Pressure) Setting (DUCT)
4. Installation Functions
This is the function that decides the strength of the wind for each wind level and because this function is to make the
installation easier.
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
TEMP
FAN
SPEED
OPER
MODE
When pressing the button and
button simultaneously for more than 3
seconds, the system will be entered into the
installer setting mode.
- After entering into the installer setting
mode, select the E.S.P code value by
pressing the button.
* E.S.P code value : 03
1
Select the desired air flow rate with
the button. Whenever pressing
the button, [SLo
→
Lo
→
Med
→
Hi
→
Po] will
be indicated.
2
Select the desired air flow rate value with
the temperature up(s), down(t) button.
* E.S.P value range : 0~255
-
E.S.P value will be indicated at the upper
right section of the display window.
3
When pressing the button, currently
established E.S.P value will be set up.
4
When pressing the button and button
simultaneously for more than 3 seconds after the
setting has been completed, the setting mode will
be released.
- If there isn’t any button input for more than
25 seconds, the installer setting mode will
also be released.
5
OPER
MODE
OPER
MODE
FAN
SPEED
FAN
SPEED
OPER
MODE
• Precaution shall be taken not to alter the E.S.P value corresponded to each air flow section.
• E.S.P value can be varied according to the products.
• In the case of going to the next air flow rate stage by pressing the fan-speed button during the setup of the
E.S.P value, the E.S.P value of previous air flow rate will be maintained by remembering the E.S.P value
prior to the shift.