2014 960-914-06 (General SVC)

- 19 -
Only for training and service purposes
4.2 E.S.P. (External Static Pressure) Setting (Cassette)
Function Code Pressure
Press button for 4 seconds to enter the installer
setting mode until timer segment displays “01:01”.
1
Select static pressure by pressing button.
(01:V-H, 02:F-H, 03:V-L, 04:F-L)
3
Press button to save.
4
5
Pressing button will exit settings mode.
After setup, it automatically gets out of setup mode if there is no button
input for 25 seconds.
When exiting without pressing set button, the manipulated value is not
reflected.
If pressing button repeatedly, it moves to static pressure
selection menu as picture below.
2
This function is applied to only duct type. Setting this in other cases will cause malfunction.
Pressure selection
Function
Zone state ESP standard value
01 V-H Variable High
02 F-H Fixed High
03 V-L Variable Low
04 F-L Fixed Low
<Static Pressure Setting Table>