2014 960-914-06 (General SVC)

- 30 -
Only for training and service purposes
6.11 Two Thermistor Control
TEMP
FAN
SPEED
OPER
MODE
When pressing the button and
button simultaneously for more than 3
seconds, the system will be entered into
the installer setting mode.
-
After entering into the installer setting
mode, select the thermistor sensor
setting code value by pressing the
button.
* Thermistor sensor selection code
value : 04
1
Select the desired setting value with the
temperature up(), down() button.
2
When pressing the button, currently
established thermistor sensor location
will be set up.
3
When pressing the button and
button simultaneously for more than 3
seconds after the setting has been
completed, the setting mode will be
released.
- If there isn’t any button input for more
than 25 seconds, the installer setting
mode will also be released.
4
OPER
MODE
OPER
MODE
Code value
*Setting value
01: Remote
controller
02: Indoor unit
03: 2TH
OPER
MODE
Value
h The function of 2TH has different operation characteristics according to the product.
<Thermistor Table>
This is the function to select the temperature sensor to judge the room temperature.
Temperature sensor selection Function
01 Remote controller Operation in remote controller temperature sensor
02 Indoor unit Operation in indoor unit temperature sensor
03 2TH
Cooling
Operation of higher temperature by comparing indoor unit's and wired remote
controller’s temperature.
(There are products that operate at a lower temperature.)
Heating
Operation of lower temperature by comparing indoor unit's and wired remote
controller's temperature.