Inverter PCB & Main
EEPROM check sum error
EEPROM Access error
and Check SUM error
1. EEPROM contact defect/wrong insertion
2. Different EEPROM Version
3. ODU Inverter & Main PCB assembly damage
Display
code
Title Cause of error Check point & Normal condition
n Error Diagnosis and Countermeasure Flow Chart
Is EEPROM insertion normal?
No
Yes
Recheck power and installation condition
1.Check EEPROM insert direction/connection condition
2.Check EEPROM Check SUM
Replace if abnormality found
Is inverter PCB assembly normal?
No
Yes
Replace inverter PCB assembly
Yes
MAIN PCB assembly normal?
No
Replace MAIN PCB assembly
Check Point
- Check the EEPROM Check sum & Direction
* AUUW24GD2 [MR24UY3J]
WARNING
Before checking PCB or each outdoor electric parts, wait for 3 minutes after the power is off. When measuring at standby state
of power supply, after checking the measurement mode of the meter, be careful of the short-circuits with other parts.