DWC1 Thermostat Installation and Operations Manual

Owner’s & Installation Manual 15
ENGLISH
Installation instruction
Function Code Pressure
Press button for 4 seconds
to enter the installer setting
mode until timer segment
displays “01:01”.
1
Select static pressure by pressing
button.
(01:V-H, 02:F-H, 03:V-L, 04:F-L)
3
Press button to save.
4
5
Pressing button will exit settings mode.
After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
When exiting without pressing set button,
the manipulated value is not reflected.
If pressing button repeatedly, it
moves to static pressure selection menu
as picture below.
2
Installer Setting - Static Pressure Setting
This function is applied to only duct type. Setting this in other cases will cause malfunction.
Pressure selection
Function
Zone state ESP standard value
01 V-H Variable High
02 F-H Fixed High
03 V-L Variable Low
04 F-L Fixed Low
<Static Pressure Setting Table>