DWC1 Thermostat Installation and Operations Manual
Owner’s & Installation Manual 15
ENGLISH
Installation instruction
Function Code Pressure
Press button for 4 seconds
to enter the installer setting
mode until timer segment
displays “01:01”.
1
Select static pressure by pressing
button.
(01:V-H, 02:F-H, 03:V-L, 04:F-L)
3
Press button to save.
4
5
Pressing button will exit settings mode.
❈ After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
❈ When exiting without pressing set button,
the manipulated value is not reflected.
If pressing button repeatedly, it
moves to static pressure selection menu
as picture below.
2
Installer Setting - Static Pressure Setting
This function is applied to only duct type. Setting this in other cases will cause malfunction.
Pressure selection
Function
Zone state ESP standard value
01 V-H Variable High
02 F-H Fixed High
03 V-L Variable Low
04 F-L Fixed Low
<Static Pressure Setting Table>