Installation Manual 24-36YJ
14
ENGLISH
1 Align the center of the pipes and sufficiently
tighten the flare nut by hand
2 Tighten the flare nut with a wrench
3. When needed to extend the drain hose of
indoor unit, assembly the drain pipe as
shown on the drawing.
Indoor unit tubing Flare nut Pipes
Wrench
Indoor unit tubing
Open-end wrench
(fixed)
Connection
pipe
Flare nut
Vinyl tape(narrow)
Adhesive
Drain pipe
Indoor unit drain hose
Outside Diameter Torque
mm inch kgf·cm N·m
Ø6.35 1/4 180~250 17.6~24.5
Ø9.52 3/8 340~420 33.3~41.2
Ø12.7 1/2 550~660 53.9~64.7
Ø15.88 5/8 630~820 61.7~80.4
Connecting the installation pipe
and drain hose to the indoor unit.
Wrap the insulation material
around the connecting portion.
1 Overlap the connection pipe insulation ma-
terial and the indoor unit pipe insulation
material. Bind them together with vinyl tape
so that there may be no gap.
2 Set the tubing cutting line upward. Wrap
the area which accommodates the rear
piping housing section with vinyl tape.
3 Bundle the piping and drain hose together
by wrapping them with vinyl tape sufficient
enough to cover where they fit into the rear
piping housing section.
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Gas Pipe
Liquid Pipe
Cutting Line
Cutting Line
Good Case Bad Case
Wrap with vinyl tape
Drain hose
Pipe
Vinyl tape(wide)
Insulation material
* Tubing cutting line have to be upward.
Indoor Outdoor
Indoor Unit
Drain hose
Indoor Unit
Drain hose
Insulation
(More than 100~300mm
length and 7mm thickness)
Extension
drain hose