Installation Manual 24-36YJ

25
ENGLISH
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
CAUTION
Capacity is based on standard length and maximum allowable length is on the basis of
reliability. Additional refrigerant must be charged after 7.5m(24.6ft).
!
Operation ranges
Mode Indoor temperature Outdoor temperature
Cooling 18°C ~ 32°C (64.4°F ~ 89.6°F)
-10°C{-18°C}*~48°C(14°F{-0.4°F}*~118.4°F)
Heating 16°C ~ 30°C (60.8°F ~ 86°F) -20°C ~ 24°C (-4°F ~ 75.2°F)
The table below indicates the temperature ranges the air conditioner can be Operated within.
{ }* : use wind baffle kit
Capacity
(Btu/h)
Pipe Size
Standard
Length
m(ft)
Max.
Elevation
m(ft)
Min
Length
m(ft)
Max.
Length
m(ft)
Additional Refrig-
erant for longer
than 7.5m(24.6ft)
GAS LIQUID
mm inch mm inch g/m oz/ft
24k, 30k, 36k Ø15.88 5/8 Ø9.52 3/8 7.5(24.6) 30(98.4) - 50(164) 35 0.38
Piping Length and Elevation