2014 960-914-05(4-23)

1. Specification
Indoor
Model Name
MD36Y3J
Power Supply
208/230, 1, 60
Power Input
-
Running Current
1.6
Casing Color
-
Dimensions
Body
W x H x D
1,230 × 380 × 590
W x H x D
48-7/16 x 14-31/32 x 23-7/32
Net Weight
Body
56.5(114.6)
Heat Exchanger
(Row x Column x Fins per inch) x No.
(3 x 16 x 18) x 1
Face Area
2
2
0.36 (3.87)
Fan
Type
Sirocco Fan
Air Flow
Rate
High-static Mode
(Factory Set)
H / M / L
3
32.0 / 27.0 / 20.0
H / M / L
3
1,130 / 953/ 706
External Static
Pressure
Pa (mmAq)
100.0(10.2)
Fan Motor
Type
BLDC
Output
350 x 1
Dehumidification Rate
5.0 (10.6)
Sound Pressure Level
H / M / L
39 / 38 / 37
Sound Power Level
Cooling
56
Piping
Connections
Liquid
Ø
9.52 (3/8)
Gas
Ø
15.88 (5/8)
Drain (O.D. / I.D.)
Ø
32.0(1-1/4) / 25.0(31/32)
Safety Devices
Fuse
-
Power and Communication Cable (included Earth)
2
4C x 0.75 (18)
Note:
1.
All data are based on the following conditions:
- Cooling Temperature : Indoor 26.7(80) DB / 19.4(67) WB
Outdoor 35°C(95) DB / 23.9(75) WB
- Heating Temperature : Indoor 21.1(70 ) DB / 15.6(60) WB
Outdoor 8.33(47) DB / 6.11(43) WB
- Piping Length : Interconnecting Piping Length : 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2.
Wiring cable size must comply with the applicable local and national code.
3.
Due to out policy of innovation some specifications may be changed without notification.
4.
Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased (maximum 3dB(A)) owing to ambient conditions during operation.
- 2 -