2014 960-914-06 (General SVC)

- 51 -
Only for training and service purposes
Check the wire
connection (Open,
Soldered poorly)
Drain pump check
Check drain tube
installation
Is it normal ?
Check the level of
water (Float moves top
position)
Is it normal ?
Check the wire
connection (Open,
Soldered poorly)
Is the float
switch clean ?
Yes
Yes
No
Check Drain Pump
Yes
No
Correct connection
Or re-soldering PCB
Is the resistance of
Drain Pump? Normal
( about 400 ) ?
Yes
No
Change the Drain Pump
Is the drain
pump clean ?
Yes
No
Clean drain pump
No
Clean float switch
Is the resistance of f
loat switch normal
(short) ?
Yes
No
Change the float switch
Is it normal ?
No
Correct connection
Or re-soldering PCB
Check Flow Chart
CN-D/Pump
CN-Float
04
Drain pump
/ Float switch
• Float switch open.
(Normal : short)
• Water over flow
• The connection of wire (Drain pump/ Float switch)
Drain pump power input. (230V)
• Drain tube installation.
• Indoor unit installation. (Inclination)
Display
code
Title Cause of error Check point & Normal condition
Check Point
1. Check the wire connection. (Open / Short) Repair the connection
2. Check the soldering state of connector. (Soldered poorly) Repair or Change the PCB.
3. Check the volt. Of main PCB power source. (DC 12V) Repair or Change the main PCB.
4. Check the installation of wired remote controller. (Noise interference) Adjust the state of installation
To change drain pump assmbly for service, first separate c/box and disassemble drain pump assembly for
LHN240HV.