Multi Zone Service Manual - General

- 14 -
Only for training and service purposes
3. Installation Functions
Part 2 Functions & Controls
This is the function that decides the strength of the wind for each wind level and because this function is to make the instal-
lation easier.
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
• Precaution shall be taken not to alter the E.S.P value corresponded to each air flow section.
• E.S.P value can be varied according to the products.
• In the case of going to the next air flow rate stage by pressing the fan-speed button during the setup of the E.S.P value,
the E.S.P value of previous air flow rate will be maintained by remembering the E.S.P value prior to the shift.
3.1 How to Set E.S.P. on the remote controller?
TEMP
FAN
SPEED
OPER
MODE
When pressing the button and
button simultaneously for more than 3
seconds, the system will be entered into the
installer setting mode.
* E.S.P code value : 03
1
Select the desired air flow rate with
the button. Whenever pressing
the button, [SLo
Lo
Med
Hi
Po] will
be indicated.
2
Select the desired air flow rate value with
the temperature up(s), down(t) button.
* E.S.P value range : 0~255
-
E.S.P value will be indicated at the upper
right section of the display window.
3
When pressing the button, currently
established E.S.P value will be set up.
4
When pressing the button and button
simultaneously for more than 3 seconds after the
setting has been completed, the setting mode will
be released.
- If there isn’t any button input for more than
25 seconds, the installer setting mode will
also be released.
5
OPER
MODE
FAN
SPEED
FAN
SPEED
OPER
MODE