Ductless Brochure

PERFORMANCE RATINGS Single Zone Wall-Mounted - Heat Pump
24k 30k 36k
SYSTEM MODEL NO. M24YJ M30YJ M36YJ
INDOOR MODEL MW24Y3J MW30Y3J MW36Y3J
OUTDOOR MODEL MR24Y3J MR30Y3J MR36Y3J
SPECIFICATIONS
CAPACITY COOLING (RATED) Btu 22,000 30,000 33,000
CAPACITY COOLING (MIN~MAX) Btu 3,070~30,030 3,070~34,000 3,070~34,000
CAPACITY HEATING
@
47
0
F (RATED) Btu 27,000 32,000 35,200
CAPACITY HEATING
@
17
0
F (RATED) Btu 17,900 21,200 23,200
CAPACITY HEATING (MIN~MAX) Btu 3,070~38,898 3,070~38,900 3,070~38,900
COOLING AMPS 7.9 13.4 17.0
HEATING AMPS 10.7 13.9 16.2
SENSIBLE HEAT RATIO .72 .78 .78
SEER 21.5 19.0 17.5
EER 12.5 10.0 8.2
HSPF 11.0 10.0 10.0
ENERGY STAR YES No No
MOISTURE REMOVAL Pts/h 5.5 6.0 6.5
AIRFLOW (QUIET, LOW, MED, HIGH) CFM 300/389/512/600 459/530/706/848 459/530/706/848
SOUND RATING - INDOOR dB-A 33 / 39 / 43 / 46 33 / 39 / 44 / 49 37 / 40 / 44 / 49
SOUND RATING - OUTDOOR dB-A 54 55 55
OPERATING RANGE COOLING (WIND BAFFLE) °F 14(0)~118 14(0)~118 14(0)~118
OPERATING RANGE HEATING °F -4~75 -4~75 -4~75
EST. YEARLY OPERATING COST $ 158 270 395
ELECTRICAL DATA
POWER SOURCE V 208/230/60/1 208/230/60/1 230/208/60/1
MINIMUM AMPACITY A 19 19 19
COOLING WATTS W 1760 3000 4024
HEATING WATTS W 2380 3100 3840
MAX. TD FUSE/BREAKER A 35 35 35
POWER AND COMMUNICATION CABLE
No. x AWG
4 x 14 4 x 14 4 x 14
REFRIGERATION SYSTEM
REFRIGERANT R410A R410A R410A
COMPRESSOR TYPE Twin Rotary Twin Rotary Twin Rotary
CONNECTIONS Flare Flare Flare
LIQUID LINE O.D. in 3/8 3/8 3/8
SUCTION LINE O.D. in 5/8 5/8 5/8
FACTORY PRECHARGE ft 25 25 25
REFRIGERANT CHARGE oz 78 78 78
MIN./MAX. LINE LENGTH ft 10~164 10~164 10~164
MAX. HEIGHT DIFFERENCE ft 98 98 98
DIMENSIONS & WEIGHT
INDOOR UNIT
W X H X D in 46-7/8 x 13-5/8 x10-3/8 46-7/8 x13-5/8 x 10-3/8 46-7/8 x 13-5/8 x 10-3/8
NET WEIGHT lbs 40 40 40
SHIPPING WEIGHT lbs 46 46 46
OUTDOOR UNIT
W X H X D in 34-5/16 x 31-1/2 x12-5/8 34-5/16 x 31-1/2 x12-5/8 34-5/16 x 31-1/2 x12-5/8
NET WEIGHT lbs 125 125 125
SHIPPING WEIGHT lbs 132 132 132
TOTAL NET WEIGHT lbs 165 165 165
TOTAL SHIPPING WEIGHT lbs 178 178 178
Your operating costs will depend on your utility rates and use. The estimated operating cost is based on a electricity cost of $ .12 per kWh.
For more information, visit www.ftc.gov/energy.
Due to continuing research in new energy-saving technology,
specications are subject to change without notice.
SPECIFICATIONS
19