Ductless Brochure

PERFORMANCE RATINGS Single Zone - The Insider
Concealed Ducted Heat Pumps
24k 36k
SYSTEM MODEL NO. D24YJ D36YJ
INDOOR MODEL MD24Y3J MD36Y3J
OUTDOOR MODEL MR24UY3J MR36UY3J
SPECIFICATIONS
CAPACITY COOLING (RATED) Btu 24,000 36,000
CAPACITY COOLING (MIN~MAX) Btu 9,700~26,700 16,000~41,400
CAPACITY HEATING
@
47
0
F (RATED) Btu 27,000 40,000
CAPACITY HEATING
@
17
0
F (RATED) Btu 17,600 24,600
CAPACITY HEATING (MIN~MAX) Btu 10,900~30,000 17,500~48,000
COOLING AMPS 15.1 20.8
HEATING AMPS 15.1 21.4
SENSIBLE HEAT RATIO .68 .67
SEER 17.0 17.6
EER 12.0 12.1
HSPF 10.0 9.2
ENERGY STAR No No
MOISTURE REMOVAL Pts/h 7.0 10.6
AIRFLOW (LOW, MED, HIGH ) CFM 530 / 618 / 688 706 / 953 / 1,130
SOUND RATING - INDOOR H/M/L dB(A) 38/36/35 39/38/37
SOUND RATING - OUTDOOR dB(A) 62 67
OPERATING RANGE (COOLING) °F 5~118 5~118
OPERATING RANGE (HEATING) °F -4~64 -4~64
EST. YEARLY OPERATING COST $ 180 268
ELECTRICAL DATA
POWER SOURCE 208/230/60/1 208/230/60/1
MINIMUM AMPACITY A 18.1 24.5
COOLING WATTS W 2000 2910
MAX. TD FUSE/BREAKER A 30 40
POWER AND COMMUNICATION CABLE
No. x AWG
4 x 14 4 x 14
REFRIGERATION SYSTEM
REFRIGERANT R410A R410A
COMPRESSOR TYPE Twin Rotary Twin Rotary
CONNECTIONS Flare Flare
LIQUID LINE O.D. in 3/8 3/8
SUCTION LINE O.D. in 5/8 5/8
FACTORY PRECHARGE ft 25 25
REFRIGERANT CHARGE oz 71 120
MIN./MAX. LINE LENGTH ft 25~164 25~246
MAX. HEIGHT DIFFERENCE ft 98 98
DIMENSIONS & WEIGHT
INDOOR UNIT
W X H X D in 46-9/16 x 11-3/4 x 17-3/4 48-1/2 x 15 x 23-1/4
NET WEIGHT lbs 73 125
SHIPPING WEIGHT lbs 95 139
OUTDOOR UNIT
W X H X D in 37-7/16 x 32-7/8 x 13 37-7/16 x 54-3/8 x 13
NET WEIGHT lbs 132 203
SHIPPING WEIGHT lbs 146 227
TOTAL NET WEIGHT lbs 205 327
TOTAL SHIPPING WEIGHT lbs 240 366
Your operating costs will depend on your utility rates and use. The estimated operating cost is based on a electricity cost of $ .12 per kWh.
For more information, visit www.ftc.gov/energy.
Due to continuing research in new energy-saving technology,
specications are subject to change without notice.