2014 Commercial Ductless Brochure

PERFORMANCE RATINGS Single Zone Cassette H/P
24k 36k
SYSTEM MODEL NO. C24YJ C36YJ
INDOOR MODEL MC24Y3J MC36Y3J
OUTDOOR MODEL MR24UY3J MR36UY3J
SPECIFICATIONS
CAPACITY COOLING (RATED) Btu 24,000 36,000
CAPACITY COOLING (MIN~MAX) Btu 9,700~26,700 14,000~42,000
CAPACITY HEATING
@
17
0
F (RATED) Btu 27,000 40,000
CAPACITY HEATING (MIN~MAX) Btu 10,900~30,000 14,500~45,000
COOLING AMPS 15.1 20.2
HEATING AMPS 15.1 20.8
SENSIBLE HEAT RATIO .77 .76
SEER 17.0 19.0
EER 12.5 13.5
HSPF 9.7 9.5
ENERGY STAR * Yes Yes
MOISTURE REMOVAL Pts/h 5.1 7.7
AIRFLOW (LOW, MED, HIGH ) CFM 459 / 530 / 600 918 / 989 / 1,060
SOUND RATING - INDOOR dB(A) 57 65
SOUND RATING - OUTDOOR dB(A) 62 67
OPERATING RANGE (COOLING) °F 5~118 5~118
OPERATING RANGE (HEATING) °F -4~64 -4~64
EST. YEARLY OPERATING COST $ 172 240
ELECTRICAL DATA
POWER SOURCE V 208/230/60/1 208/230/60/1
MINIMUM AMPACITY A 18.1 24.5
COOLING WATTS W 1910 2970
MAX. TD FUSE/BREAKER A 30 40
POWER AND COMMUNICATION CABLE
No. x AWG
4 x 18 4 x 18
REFRIGERATION SYSTEM
REFRIGERANT R410A R410A
COMPRESSOR TYPE Twin Rotary Twin Rotary
CONNECTIONS Flare Flare
LIQUID LINE O.D. in 3/8 3/8
SUCTION LINE O.D. in 5/8 5/8
FACTORY PRECHARGE ft 25 25
REFRIGERANT CHARGE oz 71 120
MIN./MAX. LINE LENGTH ft 25~164 25~246
MAX. HEIGHT DIFFERENCE ft 98 98
DIMENSIONS & WEIGHT
INDOOR UNIT
W X H X D in 33-1/16 x 8-1/16 x 33-1/16 33-1/16 x 11-3/8 x 33-1/16
NET WEIGHT lbs 45 54
SHIPPING WEIGHT lbs 58 65
INDOOR UNIT GRILLE** W X H X D in 37-3/8 x 15/16 x 37-3/8 37-3/8 x 15/16 x 37-3/8
INDOOR UNIT GRILLE** NET WEIGHT lbs 11 11
OUTDOOR UNIT
W X H X D in 37-7/16 x 32-7/8 x 13 37-13/32 x 54-3/8 x 13
NET WEIGHT lbs 132 203
SHIPPING WEIGHT lbs 146 227
TOTAL NET WEIGHT lbs 178 257
TOTAL SHIPPING WEIGHT lbs 203 293
Your operating costs will depend on your utility rates and use. The estimated operating cost is based on a electricity cost of $ .115 per kWh.
For more information, visit www.ftc.gov/energy.
*System meets ENERGY STAR
®
published minimums.
**Models require grille. Grille sold separately.
Due to continuing research in new energy-saving technology,
specications are subject to change without notice.
SPECIFICATIONS