Accessory EMRT2 Manual (2020)

38
20 – AUTO CHANGEOVER SET POINT OFFSET
00-04 (01°F* default setting) Select the difference between the
guest-selected set point and the heat and the cool set point when the
thermostat is in the automatic temperature control mode.
This value plus the 1st stage differential de ned in steps 02 and 04,
de nes the temperature at which the thermostat would automatically
change heating/cooling modes.
This feature allows adjusting the deadband between the heat and the
cool set points in automatic changeover mode in order to avoid the
system from bouncing back and forth between heating and cooling
under normal operating conditions.
.
Custom Energy Savings Settings