PRODUCT PROFILE ZONEAIRE® PREMIER Packaged Terminal Air Conditioners Features • Tangential blower wheel for fast, powerful and even air distribution • Two permanentlylubricated fan motors for quiet operation • EERs up to 13.0; COPs up to 3.6 • 2 heating and cooling fan speeds and AUTO mode ® FreshAire IAQ Ready • A full complement of Indoor Air Quality Products has been certified through installation and testing to ensure exceptional air quality is achieved when FreshAire IAQ accessories are added.
PRODUCT FEATURES DIGITAL TEMPERATURE READOUT By digitally monitoring the desired room temperature, the room is controlled more precisely than conventional systems. The large, easy-to-read LED display can show either the setpoint or actual room temperature as selected by owner. ONE-TOUCH OPERATION When the unit is powered off, the unit can be returned directly to heating or cooling mode by pressing the ‘Heat’ or ‘Cool’ buttons without the confusing power up sequence of some controls.
PRODUCT FEATURES ELECTRONIC TEMPERATURE LIMITING By limiting the operating range, the property can save energy by eliminating “max cool” or “max heat” situations common with older uncontrolled systems. The new electronic control allows owners to set operating ranges for both heating and cooling independently of one another. DIAMONBLUE ADVANCED CORROSION PROTECTION® Diamonblue Advanced Corrosion Protection® protects the outdoor coil from harsh environments. Standard on all models.
CHASSIS SPECIFICATIONS PTAC Electric Heat models Models ending in ‘K’ are 230/208V, models ending in ‘R’ are 265V PDE07K PDE07R PDE09K PDE09R PDE12K PDE12R PDE15K PDE15R PERFORMANCE DATA: Cooling Btu 7200/7000 7200 9400/9200 9400 11800/11600 11800 14500/14200 14500 Cooling Watts 550/535 550 775/760 775 1015/1000 1015 1390/1365 1390 Energy Efficiency Ratio, EER 13.0/13.0 13.0 12.1/12.1 12.1 11.6/11.6 11.6 10.4/10.4 10.4 Moisture Removal (pints/hr.) 1.7 1.7 2.1 2.1 2.
COOLING & HEATING PERFORMANCE PDE 230V - Extended Cooling Performance OUTDOOR DRY BULB TEMP. (DEGREES F AT 40% R.H.) 85 95 105 75 110 INDOOR WET BULB TEMP. (DEGREES F AT 80 F D.B.) PDE07 PDE09 PDE12 PDE15 Btu WATTS AMPS SHR Btu WATTS AMPS SHR Btu WATTS AMPS SHR Btu WATTS AMPS SHR 72 8467 449 2.2 0.59 11054 632 3.1 0.58 13877 828 4.1 0.51 17052 1134 5.1 0.46 67 8143 456 2.2 0.8 10631 642 3.1 0.79 13346 841 4.1 0.70 16400 1152 5.2 0.62 62 7538 461 2.3 0.98 9842 649 3.1 0.96 12355 851 4.1 0.
COOLING & HEATING PERFORMANCE PDH 265V - Extended Cooling Performance OUTDOO R DRY BU LB TEM P. (DEG REES F AT 40% R.H.) 75 85 95 105 110 IN DOO R WET BU LB TEM P. (DEG REES F AT 80 F D.B.) PDE07 PDE09 PDE12 PDE15 Btu WAT TS A M PS SH R Btu WAT TS A M PS SH R Btu WAT TS A M PS SH R Btu WAT TS A M PS SH R 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 8467 449 2 0.59 11054 632 2.7 0.58 13877 828 3.5 0.51 17052 1134 4.5 0.46 8143 456 2 0.8 10631 642 2.7 0.79 13346 841 3.5 0.
ELECTRIC HEAT DATA Electric Heat Data PDE/PDH07K PDE/PDH07R HE ATER WAT TS 2450 2003 3450 2821 VOLTAGE 230 208 230 208 HE ATING BTU 8300 6800 11700 9600 8300 11700 HE ATING CURRENT (AMPS) 10.7 9.7 15.0 13.6 9.3 13.1 MINIMUM CIRCUIT AMPACIT Y 14.0 14.0 19.0 19.0 12.0 17.0 15.0 15.0 20.0 20.0 15.0 20.
MODEL IDENTIFICATION / COMPONENTS PTAC/PTHP Model Identification Guide PD H 07 K 3 S G A Series PD = Friedrich Digital PTAC Engineering Digit System X = Accessory E = Cooling with electric heat H = Heat Pump with auxiliary heat Design Series Note: All PTAC models with a C design series or later come standard with Diamonblue seacoast protection and digital controls. NOMINAL CAPACITY 07 = 7,000 Btu 09 = 9,000 Btu 12 = 12,000 Btu 15 = 15,000 Btu Chassis S = Standard VOLTAGE K = 230/208V - 1 Ph.
ZoneAire® Premier Series PTAC Cooling with Electric Heat, Heat Pump PURCHASER P.O.
INSTALLATION Typical Wall Sleeve Installation (PDXWSA) ELECTRICAL RECEPTACLE PDXWSA Wall Sleeve Dimensions: 16" H x 42" W x 13 3/4" D 42-¼" MIN. LINTEL TO SUPPORT MASONRY WALLS 16-¼" 60" MAX. Front Cover Dimensions: 16" H x 42" W x 7 3/4" D Cut-Out Dimensions: 16 1/4" x 42 1/4" 20" MAX.
ACCESSORY INSTALLATION Internal Drain Kit Location and Installation (PXDR10) SCREW WALL SLEEVE OPTIONAL AREA GASKET PREFERRED AREANO FOAM INSULATION MOUNTING PLATE DRAIN TUBE NUT SIDE VIEW OPTIONAL AREA MUST BE 18”-21” CENTERED FROM SIDEWALLS TO ENSURE DRAINAGE PXDR10 DRAIN KIT 3" NOTE: IF THE DRAIN MUST BE LOCATED IN THE OPTIONAL AREA, THE FOAM INSULATION MUST BE CUT AWAY AND REMOVED TO ALLOW ACCESS TO THE DRAIN.
HVAC Engineering Specifications Digital Packaged Terminal Air Conditioners & Heat Pumps Cooling: 7000 – 14500 Btu Heating: 5800 – 13300 Btu (Heat Pump) 6800 – 17000 Btu (Electric Heat) Friedrich Models: ZoneAire Premier PDE – Cooling with electric heat PDH – Heat Pump with electric heat All units shall be factory assembled, piped, wired and fully charged with R-410A. All units shall be certified in accordance with ARI Standard 310 for air conditioners and ARI standard 380 for heat pumps.
ACCESSORIES New Construction Accessories PDXWSA WALL SLEEVE Galvanized zinc coated steel is prepared in an 11step process, then powder coated with a polyester finish and cured in an oven for exceptional durability. The wall sleeve is insulated for sound absorption and thermal efficiency, 16" H x 42" W x 13 3/4" D. PDXWSEXT18 DEEP WALL SLEEVE For walls up to 17 1/2" deep. PDXWSEXT24 DEEP WALL SLEEVE For walls up to 23 1/2" deep.
ACCESSORIES New Construction Accessories PDXDAA LATERAL DUCT ADAPTER Attaches to the Friedrich PTAC/PTHP unit to direct up to 35% of the total airflow to a second room. The unit-mounted duct plenum features a front-mounted aluminum grille that has two positions to provide the most optimal air direction. The air may be directed to either the left or the right of the unit through the supplied 3 1/2" H x 7" W x 47" L plenum. Plenum may be cut to length by the installer.
Friedrich PTAC with HEALTHY AIR DELIVERED The COVID-19 global pandemic is transforming the way the lodging industry meets the comfort and safety needs for guests. As your room air experts, Friedrich remains committed to improving guest comfort and safety with our newest innovation, FreshAire® IAQ solutions - a suite of indoor air quality accessories for use with Friedrich Air Conditioners, all with one dedicated purpose healthy indoor air.
ACCESSORIES INSTALLATION FreshAire® IAQ FreshAire® UV Single Bulb Germicidal UV Light Kit (UVT1) Step 1: PTAC Installation 1. Remove decorative front cover, remove (6) screws holding wire mesh fan guard in place 2. Remove (6) screws on each side of the metal plate above the cooling coil. 3. Install lamp with magnetic shield on the backside of metal plate. Lamp should shine down between coil and blower. Lamp will be in front of coil on PZ & PD models. Lamp cord to be fed through existing fan wire chase. 4.
ACCESSORIES INSTALLATION FreshAire® IAQ FreshAire® Purifier: iWave M Series (APWM1) iWave-M PTAC Installation Instructions: The iWave-M is a highly versatile ion generating device that is designed to be typically installed at the cooling coil; but the device can be installed in supply air as well. The iWave-M is an ideal, no replacement part device for air purification in all Friedrich PTAC’s. PTAC Installation (PZ/PD/PV) 1. Turn off power to the unit 2. Remove PTAC decorative front cover 3.
Friedrich Air Conditioning Co. 10001 Reunion Place, San Antonio, TX 78216 800.541.6645 www.friedrich.com ZONEAIRE® • PREMIER SERIES PACKAGED TERMINAL AIR CONDITIONERS LIMITED WARRANTY SAVE THIS CERTIFICATE. It gives you specific rights. You may also have other rights which may vary from state to state and province to province In the event that your unit needs servicing, contact your nearest authorized service center.
Friedrich Air Conditioning Co. l 10001 Reunion Place, Suite 500 l San Antonio, TX 78216 l 877.599.5665 l www.friedrich.com PP_PTACPRE_2021_5.20.