21 – SETBACK SET POINTS / AUTO-RESTORE
00 When room is unoccupied and the thermostat is in the setback mode or
turned off, it will NOT maintain the temperature between heat and cool
setback set points;
When guest enters the room, the thermostat will be turned off - it will
not automatically restore the most recent guest settings;
01 When room is unoccupied and the thermostat is in the setback mode or
turned off, it will maintain the temperature between heat and cool setback
set points;
When guest enters the room, the thermostat will be turned off - it will
not automatically restore the most recent guest settings;
02 When room is unoccupied and the thermostat is in the setback mode or
turned off, it will NOT maintain the temperature between heat and cool
setback set points;
When guest enters the room, the thermostat will automatically restore
the most recent guest settings;
03 * When room is unoccupied and the thermostat is in the setback mode or
turned off, it will maintain the temperature between heat and cool setback
set points;
When guest enters the room, the thermostat will automatically restore
the most recent guest settings.