RemoteThermostatand LowVoltageControlConnections
Remote Thermostat
All Friedrich PD model PTAC units are factory configured to be
controlled by either the chassis mounted Smart Center or a 24V
single stage remote wall mounted thermostat. The thermostat
may be auto or manual changeover as long as the control
configuration matches that of the PTAC unit.
To control the unit with a wall mounted thermostat follow
the steps below:
1) With the front cover removed locatethe lowvoltage terminal
strip at the lower portion of the Smart Center.
2) Remove the jumper between the 'GI2and GH' terminals.
3) The control is now configured for control by a wall thermo-
stat. The Smart Center will no longer control the unit.
4) If desired the accessory escutcheon kit (PDXRT) is to be
used, install it over the existing control panel.
Note: Torevert backtothe Smart Centercontrolof the unitreplace
the jumper wire between the 'GI2 and 'GH' terminals that was
removed in step 1.
Thermostat Connections
C = Common Ground
W = Call for Heating
Y = Call for Cooling
R = 24V Powerfrom Unit
GL = Call for Low Fan
GH = Callfor High Fan
B = Reversing Valve Energized in heating mode
(PDH Models Only)
*If only one G terminal is present on thermostat connect to GL
for low fan or to GH for high fan operation.
Figure13
Control board with optional PDXRTescutcheon kit installed