AppendixA: RemoteThermostatUnit Installation
RemoteThermostatSelection& WiringGuidelinesfor
PackagedTerminalAirConditioners
Follow the instructions and recommendations of the thermostat
manufacturer for installation and wiring. Do not use a conventional
heat pump thermostat with emergency electric heat selection for
our heat pumpunits. Our units make an automatic decision about
turning on electric heat if the heating demand cannot be met by the
heat pump due to low outdoor temperatures.
Manual Changeover Thermostat
For Heat Pump equipped units: A single stage, heat/cool
thermostat with aterminalfor a reversingvalve operation isrequired.
Terminal "B" should be continuously energized in the heat mode
and terminal "G" should be energized whenever there is a call for
heating or cooling. Typically, a heat/cool thermostat designed for
use with electric heat systems will meet the above requirements.
NOTE: This unit is designed for use with a single stage thermostat only. Improper application of the thermostat may result in property
damage, personal injury or death.
Honeywell Thermostat Terminal Designation:
TERMINAL LETTER OPERATION CONTACT MADE
Y Cooling During call for cooling.
W Heating During call for heating.
G Fan Continuous if the slider is inthe "Fan" position,otherwise, intermittent.
C Common Terminal For thermostats requiring a common terminal
R 24 V to the thermostat Directly from the transformer
B (Heat Pump units Only) Reversing Valve Made continuously during call for heating.
For Non-Heat Pump equipped units: A single stage cooling and heating thermostat is required. Terminal "G" should be
energized whenever a call for heating or cooling is made. Typically a heat/cool thermostat designed for use with electric heat
systems will meet this requirement.
SimplifiedWiringExample
Unit Terminal Board
* A-Suffix models do not have a "C" terminal
I
0 @ _ v _ ® B 01
--T.plca,PTAO,PT.P..lti
[_ -- Wall thermostat
Thermostat Terminals
NOTE: It isthe installer'sresponsibilityto ensurethat all control wiring connectionsare made inaccordance with the installationinstructions.
Improper connection of the thermostat control wiring and/or tampering with the unit's internalwiring can void the equipment warranty and
may result in property damage, personal injury or death. Other manufacturer's PTACsand even older Fdedrich models may have different
control wire connections. Questions concerning proper connectionsto the unit should be directedto the factory.
17