Manual

920-087-02(9-03)
A. Installation Checklist
[]
[]
[]
[]
[]
Inspect all components and accessories for damage
before and after installation.
[] Install the recommended Condensate Drain Kits for
complete condensate removal.
Remove the cardboard wall sleeve support and grille []
weatherboard.
Check for proper wall sleeve installation in accordance
with thewall sleeve installation instructions.
Check installation of the wall sleeve foam gasket.
Check for a subbase kit or other means of structural
support which is required for ALL installations projecting
more than 8" into room.
Ensure that the chassis is installed in a 16" high x42" wide
wall sleeve that is no deeper than
13 3/4". A baffle kit is required if the sleeve exceeds that
depth.
[] Ensure that drapes, bed, bedspread, furniture, etc. DO
NOT block either return or discharge air grilles.
[] Inspect the condenser air inletand outlet for any
obstructions (shrubbery, etc,)
B. ElectricalRatingTables
All230/208 voltunitsare equippedwithpowercords.SeeAppendixBonpage 19 for wiringinstructionson 265V units.
NOTE: Use Copper Conductors ONLY. Wire sizes are per NEC, check local codes for overseas applications.
Table 1 250 V Receptacles and Fuse Types
AMPS 15 20 * 30
RECEPTACLE (_ (_ (_
MANUFACTURER PART NUMBERS
Hubbell 5661 5461 9330
P & S 5661 5871 5930
GE GE4069-1 GE4182-1 GE4139-3
Arrow-Hart 5661 5861 5700
TiME-DELAY TYPE FUSE 15 20 30
(or HACR circuit breaker)
HACR- Heating, Air Conditioning, Refrigeration
* May be used for 15 Amp applications if fused for 15 Amp
NOTE: 265 volt units are hard wired.
Table 2 Recommended branch circuit wire sizes*
Nameplate
maximum circuit breaker size AWG Wire size**
15 14
20 12
30 10
AWG -American Wire Gauge
* Single circuit from main box
** Based on copper wire, single insulated conductor at 60°C
Electric shock hazard.
Turnoff electricpowerbeforeserviceorinstallation
A_IelectricalconnectionsandwiringMUSTbe instaUedbya qualifiedelectricianand
confon'nto the NationalElectricalCodeandalllocalcodeswhich havejurisdiction
Failureto do socanrescttin propertydamage,personalinjuryand/ordeath.
Wire Size Use ONLY wiringsize recommendedfor single outlet branch circuit.
Fuse/Circuit Use ONLY type and size fuse or HACR circuit breaker indicated on unit's rating plate. Proper current protection to the unit is the responsibility of the
Breaker owner. NOTE: A time delay fuse is provided with 265V units.
Unit MUST be grounded from branch circuit through service cord to unit, or through separate ground wire providedon permanentlyconnected units.
Grounding Be sure that branch circuit or general purpose outlet is grounded. The field supplied outlet must match plugon service cord and be within reach of
service cord. Refer to Table I for proper receptacle and fuse type. Do NOT alter the service cord or plug. Do NOT use an extension cord.
The field supplied outlet must match plugon service cord and be within reach of service cord. Refer to Table 1 for proper receptacle and fuse type.
Receptacle Do NOT alter the service cord or plug. Do NOT use an extension cord.
Use recommended wire size given in Table 2 and install a single branch circuit. All wiring must comply with local and national codes. NOTE: Use
Wire Sizing copper conductors only.
11