Brochure

Table Of Contents
FRESHAIRE
®
| SPECIFICATIONS
6 | FRESHAIRE
®
SERIES PTAC
Warning: Coastal Region Installations.
Friedrich Air Conditioning recommends that owners take necessary precautions to protect the interior space, furnishings, and hardware from
corrosion when installing make-up air products in coastal applications. Our FreshAire PTAC delivers up to 52 CFM of direct outside make-up air
into the space. If installed within 2 miles of a body of salt water, due to the high salt content of coastal air and the high latent load of the make-
up air, premature corrosion will occur naturally on non-protected items. Friedrich Air Conditioning is not responsible for premature corrosion
resulting from the use of make-up air products.
Due to continuing research in new energy-saving technology, specications are subject to change without notice. Warranty limited to installa-
tions in the United States, Puerto Rico, Mexico and Canada only. See warranty documentation for full details.
FreshAire PTAC may be covered under one or more of the following patents: 10,408,504 and 10,436,457. Additional patents pending.
LISTED
ROOM AIR CONDITIONERS
183H
PVH SERIES COOLING WITH HEAT PUMPS
Model PVH09K PVH12K PVH09R PVH12R
UPC 724587439212 724587439236 724587439229 724587439243
PERFORMANCE DATA:
Cooling Capacity Btu 9600/9400 12000/11800 9600 12000
Cooling Capacity Min./Max Btu 6462-12099 7929-17142 6462-12099 7929-17142
Cooling Watts 790/775 1040/1025 800 1040
Energy Efciency Ratio EER 12.1/12.1 11.5/11.5 12.0 11.5
Reverse Heating Capacity Btu 8200/8500 11600/11800 8500 11800
Reverse Heating Capacity Min./Max. Btu 5606-11475 6995-16187 5606-11475 6995-16187
Heating Watts 710/685 970/950 710 970
COP 3.51/3.51 3.57/3.58 3.51 3.57
Moisture Removal Pts./Hr. 1.4 1.9 1.23 2.43
Sensible Heat Ratio 80% 78% 82.7% 73.7%
ELECTRICAL DATA:
Voltage (1 PHASE, 60 Hz) 230/208 230/208 265 265
Volt Range 253-187 253-187 292-239 292-239
Current Amps 4.4/4.5 4.5/5.0 3.8 4.7
Reverse Heat Amps 4.0/4.1 4.6/4.9 3.6 4.3
Power Factor 0.80 0.96 0.82 0.90
Compressor LRA N/A N/A N/A N/A
Compressor RLA 3.2 4.1 4.2 6.2
Outdoor Fan Motor HP 1/14 1/12 1/14 1/12
AIRFLOW DATA:
Indoor CFM, HIGH 400 470 400 470
Indoor CFM, LOW 250 360 290 360
Make-up Air CFM@0.05" wc 52 52 52 52
PHYSICAL DATA:
Sleeve Dimensions H x W x D 16” x 42” x 13 3/4” (all models)
Dimensions with front H x W x D 16” x 42” x 21” (all models)
Cut Out Dimensions H x W 16 1/4”x 42 1/4” (all models)
Net Weight Lbs. 115 120 115 120
Shipping Weight Lbs. 137 142 137 142
R-410A Charge Oz. 30.34 32.80 32.1 32.8
230/208V ELECTRIC HEATER RATING
(CONFIGURATION BASED ON
POWER CORD)
POWER CORD # VOLTAGE BRANCH CKT AMPS MCA WATTS
PXPCFA23015A 230/208 15 13.9 2500
PXPCFA23020A 230/208 20 19.9 3600
PXPCFA23030A 230/208 30 27.5 5000
PXPCFA26515A 265V 15 12.0 2500
PXPCFA26515A
1
265V 15 7.3 1500
PXPCFA26520 265V 20 16.8 3500
PXPCFA26530 265V 25 23.8 5000
¹ Data for Model PVH09R
PXPCFA23020A power cord comes standard on FreshAire
®
PTAC
RECEPTACLES AND FUSE TYPES
Voltage 230V 265V
Amps 15 20 30 15 15 20 25
Heater Size 2.5 kW 3.5 kW 5.0 kW 1.5 kW 2.5 kW 3.5 kW 5.0 kW
Receptacles
NEMA#
Receptacle
6-15R 6-20R 6-30R 7-15R 7-15R 7-20R 7-30R
NEMA#
Plug
6-15P 6-20P 6-30P 7-15P 7-15P 7-20P 7-30P