Service and Parts Manual (2018, 2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- Important Safety Information
- Personal Injury Or Death Hazards
- Operation of Equipment in During Construction
- Model Number Reference Guide
- Serial Number Reference Guide
- Product Features
- General Specifications 7-9k Electric Heat
- General Specifications 7-9k Heat Pump Models
- General Specifications 12-15k Electric Heat
- General Specifications 12-15k Heat Pump
- Electrical Data
- Function and Control
- Refrigeration Sequence Of Operation
- Refrigerant System Diagram
- PTAC Installation Recommendations
- Wall Sleeve Installation Instructions (PDXWS)
- Alternate Wall Installations
- PXDR10 Drain Kit Installation
- External Drain
- PXGA Standard Grille
- Chassis Install Preparation
- Chassis Installation
- How To Connect
- Install WRT2 Wireless Programmable Thermostat
- Final Inspection & Start-up Checklist
- Refrigerant Charging
- Undercharged Refrigerant Systems
- Overcharged Refrigerant Systems
- Restricted Refrigerant System
- Sealed System Method of Charging/ Repairs
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- Basic Troubleshooting
- Malfunction Analysis
- Unit Lost Power
- Control Panel Does Not Work
- Malfunction of Temperature Sensor
- E4 Function Error
- E8 Function Error
- E9 Function Error
- Electric Heater Not Running
- Electric Heater Not Running
- 7K Cool+ Electric Heat 230 V
- 9K Cool+ Electric Heat 230v and 265v
- 12K Cool+ Electric Heat 230v and 265v
- 15K Cool+ Electric Heat 230v
- 7K Cool+ Heat Pump 230v
- 9K Cool+ Heat Pump 230v and 265v
- 12K Cool+ Heat Pump 230v and 265v
- 15K Cool+ Heat Pump 230v
- PZE07K3SB,PZE09K3SB, PZE09R3SB, PZE12K3SB, PZE12R3SB, PZE15K3SB
- PZH07K3SB, PZH09K3SB, PZH09R3SB, PZH12K3SB, PZH12R3SB, PZH15K5SB
- Reference Sheet of Celsius and Fahrenheit
- Resistance Table of THERMISTORS (5K)
21 PB
OPERATION
Function and Control
2) Heating Mode
Working condition and process for heating:
When T1≤Ts -2°F(1°C), the unit is running in heating mode. Heat pump or electric heating will start depending
on the ambient temperature condition or the heating priority setting (#4 DIP SWITCH, ON- for heat pump and
OFF-for electric heating).
When T1≥Ts+ 2°F(1°C), the heating is turned OFF. Meanwhile, the fan will run at the setting fan speed for 15s
or 1 minute delay (CONSTANT FAN OFF) or run at the setting speed continuously (CONSTANT FAN ON).
When Ts-2°F(1°C) <T1<Ts+ 2°F(1°C), the unit keeps at the previous running status.
Electric heater does not work with heat pump at the same time. When T1<41°F (5°C) unit will run the
Electric heater, when T1≥41°F (5°C) the unit will run heat pump.
3) Room Freeze Protection (AUTO HEATING)
This is valid only in standby mode. The dual 8 digital tube displays “L0”.
Entry condition: If #5 DIP SWITCH is set to ON to enable the indoor freeze protection and the main board
detects the indoor ambient temperature lower than 50°F (10°C) for 3 minutes successively .
Quitting condition: When indoor ambient temperature rises to 55 °F(13°C), heating will stop.
4) Temperature Sensor Open Circuit or Short Circuit Protection
If the temperature sensor is an open circuit or a short circuit, the ERROR CODE will display on the digital
tube. If the malfunction of temperature sensor is detected for 30s, the unit will turn off.
1) 8 DIP Switch Function
(after reprogramming, disconnect the power cord and then power up again to make it effec tive)
Warning: #2 and #3 should be matched the unit type,but #2 can be switched to OFF to set as Emergency Heat
Override! This will cause the E-heater to run all the time.
1 Reserved
2 Heat pump
ON- valid; OFF-invalid
3 E-heater
ON- valid; OFF-invalid
4 Heating priority
ON-heat pump to be prior; OFF-Electric heat to be prior
5 Room freeze protection
ON- valid; OFF- invalid
6 Auto-restart
ON- valid; OFF- invalid
7 Medium fan speed for indoor fan
ON-when HIGH fan speed,is selected the output will be medium speed instead; OFF-
output is the same speed as selected.
8 Reserved