Service and Parts Manual (2018, 2019, 2020, 2021, 2022)
Table Of Contents
- INTRODUCTION
- Important Safety Information
- Personal Injury Or Death Hazards
- Operation of Equipment in During Construction
- Model Number Reference Guide
- Serial Number Reference Guide
- Product Features
- General Specifications 7-9k Electric Heat
- General Specifications 7-9k Heat Pump Models
- General Specifications 12-15k Electric Heat
- General Specifications 12-15k Heat Pump
- Electrical Data
- Function and Control
- Refrigeration Sequence Of Operation
- Refrigerant System Diagram
- PTAC Installation Recommendations
- Wall Sleeve Installation Instructions (PDXWS)
- Alternate Wall Installations
- PXDR10 Drain Kit Installation
- External Drain
- PXGA Standard Grille
- Chassis Install Preparation
- Chassis Installation
- How To Connect
- Install WRT2 Wireless Programmable Thermostat
- Final Inspection & Start-up Checklist
- Refrigerant Charging
- Undercharged Refrigerant Systems
- Overcharged Refrigerant Systems
- Restricted Refrigerant System
- Sealed System Method of Charging/ Repairs
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- Basic Troubleshooting
- Malfunction Analysis
- Unit Lost Power
- Control Panel Does Not Work
- Malfunction of Temperature Sensor
- E4 Function Error
- E8 Function Error
- E9 Function Error
- Electric Heater Not Running
- Electric Heater Not Running
- 7K Cool+ Electric Heat 230 V
- 9K Cool+ Electric Heat 230v and 265v
- 12K Cool+ Electric Heat 230v and 265v
- 15K Cool+ Electric Heat 230v
- 7K Cool+ Heat Pump 230v
- 9K Cool+ Heat Pump 230v and 265v
- 12K Cool+ Heat Pump 230v and 265v
- 15K Cool+ Heat Pump 230v
- PZE07K3SB,PZE09K3SB, PZE09R3SB, PZE12K3SB, PZE12R3SB, PZE15K3SB
- PZH07K3SB, PZH09K3SB, PZH09R3SB, PZH12K3SB, PZH12R3SB, PZH15K5SB
- Reference Sheet of Celsius and Fahrenheit
- Resistance Table of THERMISTORS (5K)
41 PB
INSTALLATION
Install WRT2 Wireless Programmable Thermostat
Installing the Thermostat
The WRT2 thermostat comes in two parts: a receiver unit that is
wired to the PTAC unit and a transmitter unit that is installed on
the wall and wirelessly communicates with the receiver unit.
Mount Receiver Unit (Figure 503)
1. Remove the cover from the front of the PTAC unit.
2. Mount the receiver unit using double-sided tape.
3.Wire each output wire into the PTAC terminal block. Ensure
that the bare end is fully seated into the connector then tighten
securely. Pull gently on wires to ensure they are secure.
Wiring Connections
Singe Stage Cool /Heat Pump PTAC Units with Electric (Auxillary)
Heat (Models PZHXXXXSB) (Figure 504)
Note 1: Make the following Installer Settings for Heat Pump units
Change over valve Type B - Set installer settings Menu #6 to HP
PZHxxxxSB
Note 2: When congured for Heat Pump operation, the “Y” wire
will be energized for during both cooling and rst-stage heating
operation.
Note 3: Connect the “W2” wire to the “W” terminal. The “W1” does
not get connected.
Single Stage Cool PTAC Units with Electric Heat (Models
PZEXXXXSB) (Figure 505)
Note 1: Connect the “W1” wire to the “W” terminal. The “W2” wire
does not get connected.
Note 2: For PTAC units with only one fan speed (single “G” fan
terminal), use the “GL” wire for wiring and Installer Settings menu
Item 12 (High Fan) must be set to “OFF”
Single Stage Cool PTAC Units with Electric Heat Disabled
(Models PZEXXXXSB) (Figure 506)
Note 1: If connecting to a Cool only PTAC unit, the “W1” and
“W2” wires do not get connected, and Installer Settings menu 03
(Available Modes) should be set to “04: Cool Only”
Refer to Digital User Conguration
Note 2: For PTAC units with only one fan speed (single “G” fan
terminal), use the “GL” wire for wiring and Installer Settings menu
Item 12 (High Fan) must be set to “OFF”
Thermostat Connections
R = 24V Power from Unit
Y = Call for Cooling
W = Call for Electric Heating
B = Reversing Valve Energized in Heating Mode
GL = Call for Low Fan
GH = Call for High Fan
C = Common Ground
*If only one G terminal is present on thermostat connect to GL
for low speed fan or to GH for high speed fan operation.*
Figure 503 (Thermostat Receiver Installation)
Figure 504(Thermostat Reciever Wiring PZHXXXXSB)
Figure 505(Thermostat Reciever Wiring PZEXXXXSB
with Electric Heat)
Figure 506(Thermostat Reciever Wiring PZEXXXXSB
with no Electric Heat)
W
Y
B
GH
GL
C
R
R
W1
Y
BR/O
GH
GL
C
W
Y
B
GH
GL
C
R
R
W2
Y
BR/O
GH
GL
C
W
Y
B
GH
GL
C
R
R
Y
BR/O
GH
GL
C