TROUBLESHOOTING
Compressor not running
Check the wiring connections.
Check the resistence of the compressor.
The normal resistance of compressor main winding(black wire to N terminal) is under 10Ω.
NOTE: In order to isolate the compressor windings, the blak and white wire will need to be disconnected prior to taking
readings.
The resistance range is 2 Ω -10 Ω.
Figure 718 Figure 719
Figure 720
Figure 721
Figure 722