Product Profile (2021)

17
iWave-M PTAC Installation Instructions: The iWave-M is a high-
ly versatile ion generating device that is designed to be typically
installed at the cooling coil; but the device can be installed in
supply air as well. The iWave-M is an ideal, no replacement part
device for air purication in all Friedrich PTAC’s.
PTAC Installation (PZ/PD/PV)
1. Turn off power to the unit
2. Remove PTAC decorative front cover
3. Afx iWave ionizer bar to the solid surface (front surface) of coil. The ionizer bar should be centered on
the coil. (see image above) Simply use the hook and loop backing on the power pack and ionization bar
and stick it across the width of the coil so the iWave-M treats the coil as well as the breathing zone.
4. Mount power bank and wiring. Positioned on the side closest to control box assembly. Typically afxed
with hook & loop to the control box assembly cover (see image above)
5. Run wires into the control box compartment to hook up to 110VAC to 240VAC power source to where
iWave- M will power on with the indoor fan. For 110/120VAC and 208/240VAC input, connect black wire (hot)
and white wire (neutral or other AC phase) to applicable electrical terminal block.
6. Trim wires to preferred length and connect to appropriate terminals. Harness/secure wires within the
equipment as necessary.
7. Reassemble the unit, reattach front cover, and turn power on.
8. Apply installation notication sticker to the outside of the control panel cover
IMPORTANT!
Turn off main power source before starting PTAC installation.
Cleaning: If required, use a wet wipe or damp cloth to clean the ionizer bar. A soft bristle brush can also be used
to clean debris from the ion emitter. Do Not expose the iWave-M to corrosive cleaners.
ACCESSORIES INSTALLATION FreshAire
®
IAQ
FreshAire
®
Purier: iWave M Series (APWM1)