Accessory RT6P Manual (2019)

RT6P
Electronic Thermostat
Installation, Operation & Application Guide
Parts Diagram
Up button
Down button
YO/BGHGLCR W
RESET
CONFIG
Specifications
Electrical rating:
24 VAC (18-30 VAC)
1 amp maximum per terminal
3 amp maximum total load
Temperature control range: 45°F to 90°F (7°C to 32°C) Accuracy: ± 1°F (± 0.5°C)
System configurations: 2-stage heat, 1-stage cool, heat pump, electric
Timing: Anti-short Cycle: 4 minutes (bypass anti-short cycle delay by returning to OFF mode
for 5 seconds)
Backlight Operation: 10 seconds
Terminations: R, C, GL, GH, O/B, Y, W
Package Contents/Tools Required
Package includes: RT6P thermostat on base, thermostat cover, wiring labels, screws and wall
anchors, Installation, Operation and Application Guide
Tools required for installation: Drill with 3/16” bit, hammer, screwdriver
Important Safety Information
WARNING!
:
This thermostat is for 24 VAC applications only; do not use on voltages over 30 VAC
All wiring must conform to local and national electrical and building codes
Do not use air conditioning when the outdoor temperature is below 50 degrees; this can damage
your A/C system and cause personal injuries
Use this thermostat only as described in this manual
To Remove Existing Thermostat
ELECTRICAL SHOCK HAZARD
– Turn off power at the main service panel by removing
the fuse or switching the appropriate circuit breaker to the OFF position before
removing the existing thermostat.
1. Turn off power to the heating and cooling system by removing the fuse or switching the appropriate
circuit breaker off.
2. Remove cover of old thermostat. This should expose the wires.
3. Label the existing wires with the enclosed wire labels before removing wires.
4. After labeling wires, remove wires from wire terminals.
5. Remove existing thermostat base from wall.
6. Refer to the following section for instructions on how to install this thermostat.
To Install Thermostat
ELECTRICAL SHOCK HAZARD
– Turn off power at the main service panel by removing
the fuse or switching the appropriate circuit breaker to the OFF position before
removing the existing thermostat.
IMPORTANT:
Thermostat installation must conform to local and national building and electrical
codes & ordinances.
Note: Mount the thermostat about five feet above the floor. Do not mount the thermostat on an
outside wall, in direct sunlight, behind a door, or in an area affected by a vent or duct.
1. Turn off power to the heating and cooling system by removing the fuse or switching the
appropriate circuit breaker off.
2. To remove cover, pull gently at the seam at the top.
3. Put thermostat base against the wall where you plan to mount it (Be sure wires will feed through
the wire opening in the base of the thermostat).
4. Mark the placement of the mounting holes.
5. Set thermostat base and cover away from working area.
6. Using a 3/16” drill bit, drill holes in the places you have marked for mounting.
7. Use a hammer to tap supplied anchors in mounting holes.
8. Align thermostat base with mounting holes and feed the control wires through slit in thermal
intrusion barrier and into wire opening.
9. Use supplied screws to mount thermostat base to wall.
10. Insert stripped, labeled wires in matching wire terminals.
CAUTION!: Be sure exposed portion of wires does not touch other wires.
11. Gently tug wire to be sure of proper connection. Double check that each wire is connected to the
proper terminal.
12. Turn on power to the system at the main service panel.
13. Configure thermostat to match the type of system you have.
14. Replace cover on thermostat by snapping it in place.
15. Test thermostat operation as described in “Testing the Thermostat”.
Terminal Designator Descriptions
R 24 VAC hot
C 24 VAC common
O/B Configurable
O – Cool active reversing valve
B – Heat active reversing valve
Y 1st stage cool, 1st stage heat for heat pumps
W 1st stage heat for non-heat pump systems, auxiliary heat for HP systems
GL Low fan
GH High fan
RT6P Output Chart
Configuration Mode Settings
The setup screens for Configuration Mode are as follows:
5. Staged Off Outputs (For HP 0 and HP B only)
Select whether the outputs for heating and cooling are staged off
independently or are satisfied simultaneously.
1 = outputs staged off independently
0 = outputs off simultaneously
Press the up or down button to set.
Press the right button to advance to the next screen.
8. Maximum Heat Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the maximum heat set temperature allowed.
Press the up or down button to select.
Press the right button to advance to the next screen.
9. Minimum Cool Setpoint (45°F to 90°F) (7°C to 32°C)
Adjust to control the minimum cool set temperature allowed.
Press the up or down button to select.
Press the right button to advance to the next screen.
10. Room Temperature Offset (+9°F to -9°F) (+4.5°C to -4.5°C)
Adjust to calibrate displayed room temperature to match actual
room temperature.
Note: When not set to 0, will display.
Press the up or down button to select.
Press the right button to advance to the next screen.
4. 2
nd
Stage Temperature Differential (1°F to 5°F) (0.5°C to 2.5°C)
(For HP 0 and HP B only)
Set the number of degrees between when stage 1 turns on and
when stage 2 turns on.
Press the up or down button to set differential value.
Press the right button to advance to the next screen.
3. 1
st
Stage Temperature Differential (1°F to 5°F) (0.5°C to 2.5°C)
Set the number of degrees between your “setpoint” temperature
and your “turn on” temperature.
Press the up or down button to set differential value.
Press the right button to advance to the next screen.
2. Temperature Scale (F or C)
Choose Fahrenheit or Celsius.
Press the up or down button to select.
Press the
right
button to advance to the next screen.
Press the up or down button to select.
Press the right button to advance to the next screen.
Icon Descriptions
Button Functions
UP Used to increase the set temperatures and to adjust
configuration settings
DOWN Used to decrease the set temperatures and to
adjust configuration settings
SYS (left) Used to change from OFF, HEAT, COOL
and HEAT/COOL modes
FAN (right) – Used to turn on and off the indoor fan
SYS (left) and FAN (right) – Used to enter and exit program operation
SYStem (left)
FAN (right)
Down button
Up button
OFF
1. Verify the RT6P is in the OFF mode.
Press the SYS (left) button until off mode displays.
2. Remove the cover of the thermostat by gently pulling near one of the
corners at the top of the thermostat.
Configuration Mode
Press the up or down button to change settings within each screen.
To exit configuration mode, press the CONFIG switch for 1 second.
Press the button to advance to the next screen.
Pressing the
left
button will return you to the previous screen.
Down
button
Up
button
Left
button
Right
button
The configuration mode is used to set the RT6P to match your heating/cooling system. The RT6P
functions with heat pump, air conditioning, or electric heat systems.
Note:
Thermostat comes configured for 1-stage heat / 1-stage cooling for use with all heat/cool and
single-stage heat pump models. For Friedrich PTHP models follow the instructions below to
configure the thermostat for two-stage heat pump operation using the ‘O’ terminal.
To configure the RT6P, perform the following steps:
3. Press the CONFIG button for 1 second while the RT6P is in OFF mode.
CONFIG
Wiring Diagrams
Heat/Cool Systems Heat pump with electric backup
7. Auxiliary Delay ON – (0-30 minutes) (For HP 0 and HP B only)
Set the delay time in minutes for auxiliary heat to be locked out
after a call for second stage. This extra savings feature is used
to temporarily lock out auxiliary heat devices, allowing just heat
pump to try to satisfy heat call.
Press the up or down button to set.
Press the right button to advance to the next screen.
7 Day Programmable
Auto Changeover
1-Stage Heat/1-Stage Cool
Systems
Configurable to: 2-stage heat
pump
Large Display With Backlight
Selectable Fahrenheit or Celsius
Mode of Operation
RT6P is a 1-stage cool/2-stage heat thermostat. It functions with air conditioning, heat pumps, or
electric heat systems. It is programmable for 7 days a week and has auto changeover capability.
The thermostat activates the heating appliance when the room temperature is below the set heat
temperature (by the differential temperature). The RT6P will stop outputting when the call for heat has
been satisfied. With heat pumps, the thermostat will not let the compressor come on for 4 minutes
after it turns off to protect your compressor.
When the room temperature is greater than the set cool temperature (by the differential temperature),
the cooling device is activated. The RT6P will stop outputting when the call for cooling is satisfied.
The thermostat will not let the compressor come on for 4 minutes after it turns off to protect your
compressor.
The RT6P has four possible operating modes: OFF, Heat, Cool and Heat/Cool mode. In off mode,
the thermostat will not turn on heating or cooling devices. In heat mode, the thermostat controls the
heating system. In the cool mode, the thermostat controls the cooling system. In the Heat/Cool mode,
the thermostat controls the heating and cooling system
The manual fan can be turned on in all operating modes using the fan button.
In program mode, the thermostat will automatically be controlled by the set program. Program mode
can function with heat mode, cool mode, or heat & cool mode. The clock display alternates with the
set temperature display for heat & cool mode.
The program schedule can be overridden by changing the set temperature (up or down button). This
puts the RT6P thermostat into a 2-hour temporary hold. After 2 hours, it will automatically return to the
program schedule.
6. Deadband (1°F to 9°F) (1°C to 5°C)
Select the minimum difference between heat set point and cool
set point when in auto changeover mode.
Press the up or down button to set.
Press the right button to advance to the next screen.
Configuration 1
ST
Cool 1
ST
Heat 2
ND
Heat
ELC Y, G W, G, B N/A
HP ‘O’ config Y, G, O Y, G Y, W, G
HP ‘B’ config Y, G Y, G, B Y, G, B, W
The RT6P thermostat is configurable for different systems. The configuration directly affects the outputs.
Use the output chart to correctly configure and wire the thermostat to your system.
1. System – Set for heat pump, non-heat pump, reversing valve operation
System Setting Reversing Valve Setting
Heat Pump
HP ‘O’ O - Energized in Cooling
Heat Pump
HP ‘B’ B - Energized in Heating
Heat/Cool and Single-
Stage Heat Pump Only
ELC N/A

Summary of content (2 pages)