INSTALLATION
PTAC Installation Recommendations
5
PTAC Installation Recommendations
PTAC. units. should. be. installed.
no. closer. than. 12". apart. when.
two. units. are. side. by. side.. . If.
three.or.more.PTAC.units.are.to.
operate .next.to.one.another.allow.
a.minimum.of.36".between.units...
Also,.a.vertical.clearance.of.60".
should. be. maintain ed. between.
units. installed.. . In. the. interior.
of. the. room. the . unit. should. be.
located. a. mini mum. of.1/4".from.
the.
.and. a. minimum.of. 36".
from .the.ceiling.
For. minor. obstr uctions.
such.as.lamp.poles.or.small.
shrubbery. a. clearance. of.
12".from.the.outdoor.louve r.
should.be.maintained.
For.major.obstructions.such.
as. a. solid. fence,. wall. or.
other. heat. rejecting. device.
like. a. condensing. unit,. a.
minimum. distance. of. 36".
should.be.kept.
For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances
below:
For PTACs on the ground floor or anyti
me obstructions are present, use the following guidelines:
The.above.suggestions .are.for.reference.only.and.do.not.represent.all.possible.installations...Please.contact.Friedrich.for.information.regarding.affects.of.other.
installation.arrangements...By.following.these.simple.reco mmendations.you.can.be.
.t hat.your.Friedri ch.PTAC.will.provide.years.of.worry .free.operation.
Figure 1
Figure 2
FRP002
PTAC
SHRUB
POLE
FENCE OR WALL
CATPCATP
TYPICAL BUILDING ( PLAN VIEW )
CONDENSING UNIT
12"
36"
36"
36"
36" MIMUMUM, MAJO
R
OBSTRUCTIONS
12" MINIMUM, MINOR
OBSTRUCTIONS
FRP001
THREE OR MORE PTACs
ADJACENT 36" MINIMUM
GROUND FLOOR PTACs
6" MINIMUM FROM GRADE
TWO ADJACENT PTACs
12" MINIMUM
TYPICAL
WINDOW
VIEW: OUTSIDE BUILDING ELEVATION
60" VERTICAL
MINIMUM
BETWEEN
PTACs
12"
6"
36"
60"