Service and Parts Manual (2016, 2017, 2015)
Table Of Contents
- INTRODUCTION
- Important Safety Information
- Personal Injury Or Death Hazards
- Operation of Equipment in During Construction
- Model Number Reference Guide
- Serial Number Reference Guide
- Product Features
- General Specifications
- 230V COOLING AND HEATING PERFORMANCE
- 265V COOLING AND HEATING PERFORMANCE
- Electric Heat Data
- Dimensions
- Electrical Data
- Function and Control
- Digital Control User Input Configuration
- Digital Control
- Refrigeration Sequence Of Operation
- Refrigerant System Diagram
- PTAC Installation Recommendations
- Wall Sleeve Installation Instructions (PDXWS)
- Alternate Wall Installations
- PXDR10 Drain Kit Installation
- External Drain
- PXGA Standard Grille
- Chassis Install Preparation
- Thermostat
- Final Inspection & Start-up Checklist
- Refrigerant Charging
- Undercharged Refrigerant Systems
- Overcharged Refrigerant Systems
- Restricted Refrigerant System
- Sealed System Method of Charging/ Repairs
- Electrical
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- Basic Troubleshooting
- Malfunction Analysis
- Troubleshootin Chart
- Heat Pump
- Remote Wall Thermostat Wiring Diagram
- Cool With Electric Heat
- Heat Pump With Electric Heat
- PZE
- PZH
- Reference Sheet of Celsius and Fahrenheit
- Resistance Table for Air Indoor Temperature Sensor
- Resistance Table for Frost Protection Indoor and Outdoor Temperature Sensors
28 PB
INSTALLATION
PTAC Installation Recommendations
5
PTAC Installation Recommendations
PTAC. units. should. be. installed.
no. closer. than. 12". apart. when.
two. units. are. side. by. side.. . If.
three.or.more.PTAC.units.are.to.
operate .next.to.one.another.allow.
a.minimum.of.36".between.units...
Also,.a.vertical.clearance.of.60".
should. be. maintain ed. between.
units. installed.. . In. the. interior.
of. the. room. the . unit. should. be.
located. a. mini mum. of.1/4".from.
the.
.and. a. minimum.of. 36".
from .the.ceiling.
• For. minor. obstr uctions.
such.as.lamp.poles.or.small.
shrubbery. a. clearance. of.
12".from.the.outdoor.louve r.
should.be.maintained.
• For.major.obstructions.such.
as. a. solid. fence,. wall. or.
other. heat. rejecting. device.
like. a. condensing. unit,. a.
minimum. distance. of. 36".
should.be.kept.
For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances
below:
For PTACs on the ground floor or anyti
me obstructions are present, use the following guidelines:
The.above.suggestions .are.for.reference.only.and.do.not.represent.all.possible.installations...Please.contact.Friedrich.for.information.regarding.affects.of.other.
installation.arrangements...By.following.these.simple.reco mmendations.you.can.be.
.t hat.your.Friedri ch.PTAC.will.provide.years.of.worry .free.operation.
Figure 1
Figure 2
FRP002
PTAC
SHRUB
POLE
FENCE OR WALL
CATPCATP
TYPICAL BUILDING ( PLAN VIEW )
CONDENSING UNIT
12"
36"
36"
36"
36" MIMUMUM, MAJO
R
OBSTRUCTIONS
12" MINIMUM, MINOR
OBSTRUCTIONS
FRP001
THREE OR MORE PTACs
ADJACENT 36" MINIMUM
GROUND FLOOR PTACs
6" MINIMUM FROM GRADE
TWO ADJACENT PTACs
12" MINIMUM
TYPICAL
WINDOW
VIEW: OUTSIDE BUILDING ELEVATION
60" VERTICAL
MINIMUM
BETWEEN
PTACs
12"
6"
36"
60"