Service and Parts Manual (2016, 2017, 2015)
Table Of Contents
- INTRODUCTION
- Important Safety Information
- Personal Injury Or Death Hazards
- Operation of Equipment in During Construction
- Model Number Reference Guide
- Serial Number Reference Guide
- Product Features
- General Specifications
- 230V COOLING AND HEATING PERFORMANCE
- 265V COOLING AND HEATING PERFORMANCE
- Electric Heat Data
- Dimensions
- Electrical Data
- Function and Control
- Digital Control User Input Configuration
- Digital Control
- Refrigeration Sequence Of Operation
- Refrigerant System Diagram
- PTAC Installation Recommendations
- Wall Sleeve Installation Instructions (PDXWS)
- Alternate Wall Installations
- PXDR10 Drain Kit Installation
- External Drain
- PXGA Standard Grille
- Chassis Install Preparation
- Thermostat
- Final Inspection & Start-up Checklist
- Refrigerant Charging
- Undercharged Refrigerant Systems
- Overcharged Refrigerant Systems
- Restricted Refrigerant System
- Sealed System Method of Charging/ Repairs
- Electrical
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- Basic Troubleshooting
- Malfunction Analysis
- Troubleshootin Chart
- Heat Pump
- Remote Wall Thermostat Wiring Diagram
- Cool With Electric Heat
- Heat Pump With Electric Heat
- PZE
- PZH
- Reference Sheet of Celsius and Fahrenheit
- Resistance Table for Air Indoor Temperature Sensor
- Resistance Table for Frost Protection Indoor and Outdoor Temperature Sensors
29 PB
INSTALLATION
Wall Sleeve Installation Instructions (PDXWS)
6
Wall Sleeve Installation Instructions (PDXWSA)
NOTE:. Insure.that.the.unit.is.only.in s talled.in.a.wall.structurally.adequate.to.support.the.unit.includin g.the.sleeve,.chassis.and.accessories...If.the.sleeve.
projects.more.than.8".i nto.the.room,.a.subbas e.or.ot her.means.of.support.MUST.be.used...Please.read.thes e.instructions.completel y.befo re.
attempting.i nstallation.
For Deep Wall Installation (Greater than 13 1/4")
See Page 9
The.following.instructions.apply.ONLY.to.walls.less.than.13.¼".in.depth..
1. The.PXDR10.Dr ain.Kit,(o ptiona l.for.new.c onstruction).see.page.10.
if.applic able,.must.be.inst alled.before.the.wall.sleeve.is.inst alled.
into.the.wall.
2. The.External.Drain.(for.new.construction.or.unit.replace ment).see.
page. 11 if.applicable,.must.be.installe d.before.the.wall.sleeve.is.
installed.into.the.wal
l.
3. From.inside.the.building,.position.the
.wall.sleeve.in.the.opening.and.
push.it.into.the.wall.until..it.protrudes.at.le ast.¼”.on.the.outside...
(See.Figure . 9, .Page.8).
4. Position.th e.wall. sleeve. with. a.slight.tilt.towards.the.outside. to.
facilitate.condensate.drainage...It.should.be.level.side-to-side.and.
the.front.should.be.¼.b ubble.higher.than.the.back.
Figure 3
Typical Wall Sleeve Installation
NOTICE
DO NOT allow any pitch toward the inside.
Flashing on all 4 sides of the opening is recommended.
Potential property damage can occur if instructions are
not followed.
WARNING
Falling Object Hazard
Not following Installation Instructions for
mounting your air conditioner can result
in property damage, injury, or death.
FRP008
20
"
MAX.
16-¼
"
42-¼
"
MIN.
LINTEL TO SUPPORT
MASONRY WALLS
ELECTRICAL
RECEPTACLE
ELECTRICAL
RECEPTACLE
WALL OPENING
WALL SLEEVE
INSULATION
INSULATION
SMOOTH SIDE OF SCREW
CLIP FACING INTO ROOM
NOTE: All 230/208V units are manufactured with a 60” power cord and all 265V units with a 18” power cord.
60
"
MAX.
13-¾
"