Service and Parts Manual (2016, 2017, 2015)
ManualsBrandsFriedrich ManualsAir Conditioners14,500 BTU Smart Packaged Terminal Air Conditioner with FriedrichLink Energy Management Thermostats, Heat Pump, Antimicrobial Air Filters, Electronic Defrost Control, Tangential Blower Wheel, Room Freeze Protection, Fresh Air Damper, Slinger Ring Technolo
Table Of Contents
- INTRODUCTION
- Important Safety Information
- Personal Injury Or Death Hazards
- Operation of Equipment in During Construction
- Model Number Reference Guide
- Serial Number Reference Guide
- Product Features
- General Specifications
- 230V COOLING AND HEATING PERFORMANCE
- 265V COOLING AND HEATING PERFORMANCE
- Electric Heat Data
- Dimensions
- Electrical Data
- Function and Control
- Digital Control User Input Configuration
- Digital Control
- Refrigeration Sequence Of Operation
- Refrigerant System Diagram
- PTAC Installation Recommendations
- Wall Sleeve Installation Instructions (PDXWS)
- Alternate Wall Installations
- PXDR10 Drain Kit Installation
- External Drain
- PXGA Standard Grille
- Chassis Install Preparation
- Thermostat
- Final Inspection & Start-up Checklist
- Refrigerant Charging
- Undercharged Refrigerant Systems
- Overcharged Refrigerant Systems
- Restricted Refrigerant System
- Sealed System Method of Charging/ Repairs
- Electrical
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- Basic Troubleshooting
- Malfunction Analysis
- Troubleshootin Chart
- Heat Pump
- Remote Wall Thermostat Wiring Diagram
- Cool With Electric Heat
- Heat Pump With Electric Heat
- PZE
- PZH
- Reference Sheet of Celsius and Fahrenheit
- Resistance Table for Air Indoor Temperature Sensor
- Resistance Table for Frost Protection Indoor and Outdoor Temperature Sensors
18 PB
SPECIFICATIONS
Electrical Data
14
Electrical Wiring for 265 Volt
Models
NOTE:. It. is. recommended. that. the. PXSB. subb ase. asse mbly,.the.
PXCJA.c onduit.kit.(or.equivalent).be.installed.on.all.hardwire.
units...If.installing.a.
.mounted.u nit,.make.sure.the.
chassis. ca n. be. removed. from. the. sleeve. for. service. and.
maintenance.
WARNING
Electrical Shock Hazard
Turn off electrical power before service
or installation.
ALL electrical connections and wiring
MUST be installed by a qualified
electrician and conform to the National
Code and all local codes which have
jurisdiction.
Failure to do so can result in property
damage, personal injury and/or death.
Power Cord Installation
All.265V.PTAC/PTHP.units.come.with.a.factory.installed.non-LCDI.
power.cord.for.use.in.a.s ubbase..If.the.unit.is.to.be.hard-wired.refer.to.
the.instructions.below.
To install the line voltage power leads and conduit
to chassis, follow the instructions below and refer
to Figures 25-27 on page 19. PXCJA Conduit Kit
is required with this setup.
1. Follow. the. removal. process. of. the. chassis’s. junction. box..
(Figure.25,.step.2,.page.19).
2. .Prepare.the.265V.(or.230V).power.cord.for.conn ection.to.the.chas-
sis’.power.co rd.connector.by.cutting.the.cord.to.the.appropriate.
length.(refer.to.Figure.26.and.follow.Figure.15)...Power.cord.harness.
selection.shown.on.Table.2.on .page.14.
TABLE 2
MODEL HEATER kW Power Cord Kit Voltage Amperage Receptacle
PZE / PZH07K 3.0 STD 230/208 15 NEMA 6-20r
PZE / PZH09K 3.0 STD 230/208 20 NEMA 6-20r
PZE / PZH12K 3.0 STD 230/208 20 NEMA 6-20r
PZE / PZH15K 5.0 STD 230/208 30 NEMA 6-30r
PZE / PZH09R 3.0 STD 265 20 NEMA 7-20r
PZE / PZH12R 3.0 STD 265 20 NEMA 7-20r