Service and Parts Manual (2016, 2017, 2015)
ManualsBrandsFriedrich ManualsAir Conditioners14,500 BTU Smart Packaged Terminal Air Conditioner with FriedrichLink Energy Management Thermostats, Heat Pump, Antimicrobial Air Filters, Electronic Defrost Control, Tangential Blower Wheel, Room Freeze Protection, Fresh Air Damper, Slinger Ring Technolo
Table Of Contents
- INTRODUCTION
- Important Safety Information
- Personal Injury Or Death Hazards
- Operation of Equipment in During Construction
- Model Number Reference Guide
- Serial Number Reference Guide
- Product Features
- General Specifications
- 230V COOLING AND HEATING PERFORMANCE
- 265V COOLING AND HEATING PERFORMANCE
- Electric Heat Data
- Dimensions
- Electrical Data
- Function and Control
- Digital Control User Input Configuration
- Digital Control
- Refrigeration Sequence Of Operation
- Refrigerant System Diagram
- PTAC Installation Recommendations
- Wall Sleeve Installation Instructions (PDXWS)
- Alternate Wall Installations
- PXDR10 Drain Kit Installation
- External Drain
- PXGA Standard Grille
- Chassis Install Preparation
- Thermostat
- Final Inspection & Start-up Checklist
- Refrigerant Charging
- Undercharged Refrigerant Systems
- Overcharged Refrigerant Systems
- Restricted Refrigerant System
- Sealed System Method of Charging/ Repairs
- Electrical
- Hermetic Components Check
- Reversing Valve Description And Operation
- Testing The Reversing Valve Solenoid Coil
- Checking The Reversing Valve
- Touch Test Chart : To Service Reversing Valves
- Compressor Checks
- Compressor Replacement
- Compressor Replacement -Special Procedure in Case of Compressor Burnout
- Basic Troubleshooting
- Malfunction Analysis
- Troubleshootin Chart
- Heat Pump
- Remote Wall Thermostat Wiring Diagram
- Cool With Electric Heat
- Heat Pump With Electric Heat
- PZE
- PZH
- Reference Sheet of Celsius and Fahrenheit
- Resistance Table for Air Indoor Temperature Sensor
- Resistance Table for Frost Protection Indoor and Outdoor Temperature Sensors
28 PB
INSTALLATION
PTAC Installation Recommendations
5
PTAC Installation Recommendations
PTAC. units. should. be. installed.
no. closer. than. 12". apart. when.
two. units. are. side. by. side.. . If.
three.or.more.PTAC.units.are.to.
operate .next.to.one.another.allow.
a.minimum.of.36".between.units...
Also,.a.vertical.clearance.of.60".
should. be. maintain ed. between.
units. installed.. . In. the. interior.
of. the. room. the . unit. should. be.
located. a. mini mum. of.1/4".from.
the.
.and. a. minimum.of. 36".
from .the.ceiling.
• For. minor. obstr uctions.
such.as.lamp.poles.or.small.
shrubbery. a. clearance. of.
12".from.the.outdoor.louve r.
should.be.maintained.
• For.major.obstructions.such.
as. a. solid. fence,. wall. or.
other. heat. rejecting. device.
like. a. condensing. unit,. a.
minimum. distance. of. 36".
should.be.kept.
For proper PTAC unit performance and maximum operating life refer to the minimum installation clearances
below:
For PTACs on the ground floor or anyti
me obstructions are present, use the following guidelines:
The.above.suggestions .are.for.reference.only.and.do.not.represent.all.possible.installations...Please.contact.Friedrich.for.information.regarding.affects.of.other.
installation.arrangements...By.following.these.simple.reco mmendations.you.can.be.
.t hat.your.Friedri ch.PTAC.will.provide.years.of.worry .free.operation.
Figure 1
Figure 2
FRP002
PTAC
SHRUB
POLE
FENCE OR WALL
CATPCATP
TYPICAL BUILDING ( PLAN VIEW )
CONDENSING UNIT
12"
36"
36"
36"
36" MIMUMUM, MAJO
R
OBSTRUCTIONS
12" MINIMUM, MINOR
OBSTRUCTIONS
FRP001
THREE OR MORE PTACs
ADJACENT 36" MINIMUM
GROUND FLOOR PTACs
6" MINIMUM FROM GRADE
TWO ADJACENT PTACs
12" MINIMUM
TYPICAL
WINDOW
VIEW: OUTSIDE BUILDING ELEVATION
60" VERTICAL
MINIMUM
BETWEEN
PTACs
12"
6"
36"
60"