Installation and Operation Manual (2021)

6
ATEX & ICEX Standards Specific to Models SH20N50AT & SH24N20AT
SH20N50AT and SH24N20AT Adhere to the following certifications:
CERTIFIED PER STD. NO. ANSI/ISA 12.12.01,2013
PER STD. NO. IEC 60079-0, 6th Edition
PER STD. NO. IEC 60079-15, 4th Edition
PER STD. NO. CAN/CSA C22.2 NO 152-92, REV 2003-06
PER STD. NO. CENELEC EN 60079-0: 2012 + A11: 2013
PER STD. NO. CENELEC EN 60079-15: 2010
CERTIFICATION DEMKO 15 ATEX 1364X
IECEX UL15.0051X
SH20N50AT & SH24N20AT Specific Conditions of
Use:
Provision shall be made to prevent the rated voltage
being exceeded by the transient disturbances of more
than 140% of the peak rated voltage.
Only for use in locations providing adequate protection
against the entry of solid foreign objects or water
capable of impairing safety.
The equipment must be installed only for use in locations
providing adequate protection against the entry of solid
foreign objects or water capable of impairing safety.
Only permanently wired cables may enter the cable
glands. The user shall provide for the required strain
relief.
Degree of protection will be safeguarded only when
sealing and cable entry fittings are properly fitted. The
Manufacturer’s instructions must be followed.
Cable Glands shall be mounted into the enclosure in
such a way that they are mechanically protected
against impact force.
To avoid the buildup of electrostatic charge,
regularly clean the unit with a damp cloth.
NOTICE: To maintain IP40 protection, the Hazardgard unit must be
installed in accordance to the installation instructions stated in this
document.