Chassis Wiring and Preparation (ATEX & IECEx Models)
Figure 34
EXTERNAL GROUND
-See Note-
NOTE: This air conditioner shall be installed in accordance with national wiring regulations of the country where installed.
Electrical connections to equipment must only be carried out by qualied personnel per NEC/CEC 501.10 (B) EN/IEC 60079-14.
Repairs affecting hazard location protection must be carried out by a qualied electrician in accordance with NEC/CEC 501.10
(B) EN/IEC 60079-19.
STEP 4 Complete junction box wiring, cover and tighten cover screws (Figure 34-6) to prevent ingress from dust and moisture.
NOTE: Per EN/IEC 60079-0, external grounding or earthing may be necessary.
If required, use provided external ground clamp which can accept two cables of up to 6mm (Figure34-7).
INSTALLATION
ELECTRICAL JUNCTION
BOX
WITH EMI FILTER
Figure 35