Manual

B. Auto Changeover Thermostat
A single stage thermostat with dual stages of heating and auto changeover is needed. The recommended Thermostat/
Subbase combination is the Honeywell T-874C/Q 674E.
ThermostatTerminal Jumper Wire to PTAC Terminal
Y & W2 YES N/A
Y N/A Y
Wl N/A W
R N/A R
G N/A G
Unit Terminal Board
: JUnnpE_
Thermostat Terminals
2. Installation
Follow Steps 1 through 5 (pages 4 and 5), then: ('/R _)
6. Locate the terminal strip on the right side of the control box. Attach
the thermostat subbase wires (field supplied) to the appropriately
labeled terminals as per widng diagram on the side of the chassis.
7.
NOTE: No connections are made to the
"C" Terminal when one of the
manufacturer's thermostat subbases is
used.
Carefully route the wires alongside the conduit
or service cord. Attach the other end of the wires
to the appropriate terminals on the thermostat
subbase. See thermostat directions for proper
widng and mounting of thermostat.
If the filter is not in place, install as shown.
mil*