3) ElectricalData (continued)
Figure6
Electrical Requirements
Note:All field wiring must comply with NEC andlocal codes. It
is the responsibility of the installerto insurethat the electrical
codes are met.
Use ONLY wiring size recommended for single
Wire Size
outlet branch circuit.
Use ONLY type and size fuse or HACR circuit
Fuse/Circuit breaker indicated on unit's rating plate (See sample
Breaker on page 6), Proper current protection to the unit is
the responsibility of the owner.
Unit MUST be grounded from branch circuit to
Grounding unit, or through separate ground wire provided on
permanently connected units. Be sure that branch
circuit or general purpose outlet is grounded,
Use recommended wire size given in tables and
install a single branch circuit. Allwidng must comply
Wire Sizing with local and national codes, NOTE: Use copper
conductors only.
Electrical RatingTables
NOTE: Use copper conductors ONLY, Wire sizes are per
NEC Check local codes for overseas applications
Recommended branch circuit wire sizes*
Nameplate AWG Wire size**
maximum circuit
breaker size
15A 14
20A 12
30A 10
AWG --American Wire Gauge
* Single circuitfrom main box
** Based on copper wire, single insulatedconductor at 60°C
Electric shock hazard.
Turn OFF electric power before service
or installation.
All electricalconnectionsandwiring MUST
be installed by a qualified electrician and
conform tothe NationalElectricalCode and
all local codes which have jurisdiction.
Failure to do so can result in property
damage, personal injury and/or death.