Installation & Operation Manual VERT-I-PAK® A-Series Single Package Vertical Heat Pump System VPAK IOM / 95991015_00
Table of Contents Warnings___________________________________________________________________________________ 3 General Specifications_______________________________________________________________________________ 4 Electrical Data_____________________________________________________________________________ 5 Electrical Specifications & Sound Data_________________________________________________________ 7 Chassis Dimensions__________________________________________________________________________ 8 Air Fl
Congratulations! The Friedrich VPAK has been carefully engineered and manufactured to provide many years of dependable, efficient operation while maintaining a comfortable temperature and humidity level. Many extra features have been built into the unit to ensure quiet operation, optimal circulation of cool, dry air, and the most economic operation. Please carefully read and follow the installation instructions and safety warnings detailed in this manual.
General Specifications MODEL VHA09K VHA09R VHA12K VHA12R VHA18K VHA18R VHA24K VHA24R TOTAL COOLING CAP. 9300 9300 11500 11500 18400 18400 22500 22500 SENSIBLE COOL CAP. 7440 7440 9085 9085 13430 13430 15750 15750 POWER (W) 845 845 1045 1045 1670 1670 2045 2045 11.0 11.0 COOLING DATA 11.0 11.0 11.0 11.0 11.0 11.0 2.5/3.4/5.0 2.5/3.4/5.0 2.5/3.4/5.0 2.5/3.4/5.0 2.5/3.4/5.0 2.5/3.4/5.0 8300 8300 10600 10600 16700 16700 EER HEATER SIZE (kW) 2.5/3.4/5.
Electrical Data- VHA09 & 12 ELECTRICAL DATA VHA09K HEATER WATTS 2050-2500 2780-3400 VHA12K 4090-5000 VOLTAGE 2050-2500 2780-3400 4090-5000 208-230 ELECTRIC HEATING BTU 7000-8500 9500-11600 13900-17000 7000-8500 9500-11600 13900-17000 ELEC. HEATING CURRENT (AMPS) 11.1-12.0 14.6-16.0 20.9-22.9 11.1-12.0 14.6-16.0 20.9-22.9 15.0 20.0 29.2 15.0 20.0 29.2 15 20 30 15 20 30 21.0 21.0 21.0 23.0 23.0 23.0 2.5KW 3.4KW 5.0KW 2.5KW 3.4KW 5.
Electrical Data- VHA18 & 24 ELECTRICAL DATA VHA18K HEATER WATTS 2050-2500 2780-3400 VHA24K 4090-5000 2050-2500 VOLTAGE 2780-3400 4090-5000 6135-7500 8180-10000 208-230 ELECTRIC HEATING BTU 7000-8500 9500-11600 13900-17000 7000-8500 9500-11600 13900-17000 ELEC. HEATING CURRENT (AMPS) 11.1-12.0 14.6-16.0 20.9-22.9 11.3-12.3 14.8-16.2 21.1-23.1 30.9-34.0 40.7-44.9 15.0 20.0 29.2 15.4 20.3 29.0 42.6 56.1 15 20 30 20 25 30 45 60 37.0 37.0 37.0 44.0 44.0 44.0 44.
Electrical Specifications & Sound Electrical Rating Table Electrical Requirements NOTE: Use copper conductors ONLY. Wire sizes are per NEC. Wire Size Use ONLY wire size recommended for single outlet branch circuit. Fuse/Circuit Breaker Use ONLY type and size fuse or HACR circuit breaker indicated on unit’s rating guide. Proper over current protection to the units is the responsibility of the owner.
Chassis Dimensions - VHA09 & VHA12 Front Side 23 1/8” Rear 23 1/8” 10” SUPPLY AIR DUCT DIAMETER 2 15/16” 10 1/8” CONDENSER INLET AIR 29 1/2” RETURN AIR 29 1/2” CONDENSER EXHAUST AIR 31” 19 1/2” 1 1/2” UNIT TOP VIEW DIMENSIONS Outside Wall 8
Chassis Dimensions - VHA18 SUPPLY AIR 10 DUCT DIAMETER ELECTRICAL ENTRY BOTH SIDES 5 1/16 2 3/16 2 1/2 11 11/16 RETURN AIR CONDENSER INLET AIR 39 3/4 42 5/8 47 15/16 31 CONDENSER EXHAUST AIR FRONT SIDE 1 1/2 REAR UNIT TOP VIEW DIMENSIONS 22 5/16" control box electrical entrance 8 3/8" 6 3/16" 4 3/16" 5 5/16" 7 3/16" 9
Chassis Dimensions - VHA24 SUPPLY AIR 20 5/8 DUCT ELECTRICAL ENTRY BOTH SIDES 6 55/64 DUCT 5 5/32 1 DUCT 15 7/16 2 1/2 RETURN AIR 46 23/32 51 7/8 CONDENSER INLET AIR 44 CONDENSER EXHAUST AIR 31 9/32 1 1/2 FRONT SIDE REAR UNIT TOP VIEW DIMENSIONS 12 19/64 1 1/2 PART NO.
Supply Air Flow Data Indoor CFM & External Static Pressure Model VHA09/VHA12 Fan Speed Low High VHA18 Low VHA24 High Low High SCFM ESP (“) 0.0” 470 520 730 800 755 805 0.05” 460 510 670 735 700 750 0.10” 430 490 630 675 660 700 0.15” 410 470 595 640 615 665 0.20” 360 440 550 600 575 625 0.25” 310 400 505 550 525 580 0.30” 260 350 455 500 485 540 0.35” -- -- 400 445 450 500 0.
Vert-I-Pak Required Minimum Clearances Building Exterior Unit Opening Requirements VPAK units must be installed on an outside wall. Confined spaces and/or covered areas should be avoided. Units must be installed no closer than 12” apart when two units are side by side. If three or more units are to operate next to one another, maintain a minimum of 60” between units or pairs of units (Figure B).
Installation Overview VHA09 & VHA12 Applicable Models VHA09K VHA09R VHA12K VHA12R Louver VPAL2/VPSC2 (Sold separately) Part A Outside Wall Plenum Exterior/ Outside Wall Filter (14” x 20”) Part B Inside Wall Plenum Unit VPAWP1-8 = 5 1/2" - 8" D x 24 1/8" W x 30 3/8" H VPAWP1-14 = 8" - 14" D x 24 1/8" W x 30 3/8" H VHA18 Applicable Models VHA18K VHA18R Large Chassis Unit (Unit height 47”) Louver VPAL2/VPSC2 (Sold separately) Part A Outside Wall Plenum Exterior/ Outside Wall Filter (14” x 20”) Part B
Installation Overview VHA24 Applicable Models VHA24K VHA24R Louver VPAL2/VPSC2 (Sold separately) Filter (18” x 20”) Part A Outside Wall Plenum Exterior/ Outside Wall Part B Inside Wall Plenum Unit VPDP2 drain pan required (Sold & shipped separately) VPAWP1-8 = 5 1/2" - 8" D x 24 1/8" W x 30 3/8" H VPAWP1-14 = 8" - 14" D x 24 1/8" W x 30 3/8" H 14
Closet Orientations & Dimensions )URQW ,QVWDOODWLRQ 7RS 9LHZ 23 1/8" 26 1/8" 23 1/8" 3" 27" 29 1/8" /HIW ,QVWDOODWLRQ 7RS 9LHZ 3 23 1/8" 27" 23 1/8" 31 1/8"
Closet View Example Closet 25" x 20" Filter (Field Supplied) Rigid Ductwork Electrical Connection Exterior Wall Flexible Ductwork VPAWP1-8/1-14 Wall Plenum Plenum Divider Thermostat Wiring VPRG4/VPRG4R Access Panel and Return Air Filter Grille Power Disconnect 3/4" FPT Drain Connection Recommended eld installed drain pan Chassis installs 2 3 / 8" into Plenum VPAWP1-8/1-14 Wall Plenum cut-out dimensions 24 5/8" wide x 30 7/8" high. VPRG4 Access Panel cutout dimensions: 27" wide by 55 3/4" high.
Wall Opening Dimensions Exterior Wall Plenum Cut-Out Dimensions (W x H): 24 5/8” x 30 7/8” 3/4” NOTE: The distance between the rough opening and the finished floor/platform must be 3/4”. If the installation will utilize an auxiliary drain pan it may not exceed 3/4” in height.
Wall Plenum Installation Parts included in Plenum kit: B Outside Plenum Half (Part A) Inside Plenum Half (Part B) A Field Supplied Parts: Sealant, attachment screws, and flashing are field supplied. Silicone sealant is recommended. Flashing Sealant VPAWP-8 adjust for walls up to 4”- 8” thick. VPAWP-14 adjust for walls up to 8” - 14” thick Shim All installations are similar.
Wall Plenum Installation Step 1 - Outside Wall Plenum Half Note: The wall plenum is not designed to carry any structural load. A load bearing header must be built above the rough opening. 1. Prepare the rough opening. The rough opening should be lined with metal or wood. The plenum will warp if sealed against concrete or brick. 2. Dry fit the outside plenum half into the rough opening and check the fit and level. 3.
Wall Plenum Installation Step 2 - Inside Wall Plenum Half Caulk all 8 Flange Corners and Unused Holes Detail A 1. Apply sealant to all 4 flange corners and unused holes. See Detail A. 2. Flash the inside of the rough opening to ensure the proper fit and level. 3. Insert inside plenum half (Part B) into outside plenum half (Part A). Ensure that Part A does not back out of the rough opening. 4. Remove the inside plenum half. 5.
Wall Plenum Installation Step 3 - Inside Wall Plenum (cont.) B Detail B NOTE: Do not place any screws, fasteners, or penetrating holes through the top or bottom of the plenum assembly. 1. Drill pilot holes on the interior of the inside plenum half (Part B) as show in Detail B. Pilot holes should be located approximately 4” from the top and bottom of the inside plenum half, on both the left and right sides. 2. Install fasteners through each pilot hole. Fastener must pass through both Part A and Part B.
Wall Plenum Installation Step 3a - Inside Wall Plenum Half VHA18 & VHA24 Drain Kit Installation Note: The VHA18 and VHA24 models require installation of the large chassis drain kit (VPDP2). Please reference the VPDP2 installation manual for more detailed instructions. 1. Cut away gasket from the of the base of the inside wall plenum half the length of the drain kit beginning from the bottom right corner. 2. Place the VPDP2 where the gasket has been removed as shown above. 3.
Louver Installation Installation of the louver PRIOR to wall plenum installation 1. 2. Hold the louver up to the outside plenum half (Part A) and line up the louver top with the very top edge of the ¾” flange. Line up the wall plenum holes with the threaded holes in the louver and securely tighten fasteners. Installation of the louver AFTER the installation of wall plenum on elevated floors From the interior of the utility closet: 1.
Final Wall Plenum and Architectural Louver Installation Louver NOTE: Ensure that the weather strip is undamaged and provides a continuous seal around the inner perimeter of the plenum. Apply silicone grease or other non-petroleum-based lubricants to the weather strip to enhance the sealing capability of the weather strip and ease installation of the air conditioner chassis. 1. Loosen the two set screws located on the top side of the divider. 2.
Chassis Installation A 1. Ensure that the wall plenum and louver are installed in accordance with the instructions listed on pages 13-18. 2. Place the chassis into the closet with the outdoor side facing the wall plenum opening. 3. Slide the chassis into the wall plenum until the plenum divider seal is established. NOTE: The Vert-I-Pak chassis must be inserted into the wall plenum so that the plenum divider gasket makes contact with the plastic condenser baffle on the unit.
Primary Drain Installation Nipple 3/4” PVC/NPT Union 3/4” FTP/SLIP Supplied 3/4” plugs Threaded end Example of field supplied DWV system Slip end NOTE: Failure to follow the following procedures may result in serious property damage. A field supplied secondary condensate pan or P-trap may be required. Check with local codes. In case of drainage system blockage, the unit base will allow excess water to flow out of the unit through the plenum and the architectural louver.
Indoor Return Air Grille and Ductwork Installation Option 1 Option 2 VPRG4/R Return Air Grille with Access Panel A field-supplied (25” x 20”) can be mounted inside the hinged access door. The door can be installed with the grille oriented at the top of the panel for improved sound attenuation. Field Supplied Return Air Grille A field supplied return air grille divorced from the access panel must have a minimum 250 square inches of free area.
Remote Thermostat and Low Voltage Control Connection Remote Thermostat Auxiliary Fan Control All Friedrich Vert-I-Pak units are factory configured to be controlled by using a single stage heat/cool remote wall mounted thermostat. The thermostat may be auto or manual changeover as long as the control configuration matches that of the Vert-I-Pak unit. The Friedrich Vert-I-Pak also has the ability to control a 24VAC relay to activate an auxiliary or transfer fan.
VHA09 & VHA12 208-230 Electrical Wiring Diagram WASHER C S HARNESS COMPRESSOR COMPRESSOR COMP RELAY VOLTAGE SWITCH "F" BLACK L1 L2 RED CIRCUIT BREAKER COIL SOLENOID FAN 1 RELAY FAN 2 RELAY RED GREEN BLOWER MOTOR BLUE SERVICE DISPLAY TO MOTOR MOUNT AMBIENT AIR SENSOR PART NO.
VHA09 & VHA12 265 Electrical Wiring Diagram WASHER A A NUT BLACK WHITE FUSE BLOCK COMPRESSOR C HARNESS COMPRESSOR S A R L1 HEAT RELAY RED " F" CIRCUIT BREAKER RED FAN 2 RELAY C WHITE CAPACITOR HERM COIL SOLENOID RV RELAY RED MOTOR GREEN BLUE OUTDOOR COIL SENSOR HEATER 2.5 KW & 3.4 KW 5.0 KW FAN 4 RELAY ORANGE WHITE INDOOR COIL SENSOR FAN 3 RELAY RELAY BLACK WIRING DIAGRAM COOL, ELECTRIC HEAT, HEAT PUMP SMALL CHASSIS, 265V HEATERS: 2.5KW, 3.4KW, 5.
VHA18 208-230 Electrical Wiring Diagram COMPRESSOR S HEAT RELAY " F" CIRCUIT BREAKER WHITE WHITE WHITE COIL SOLENOID FAN 3 RELAY HERM FAN 4 RELAY WHITE RV RELAY BLUE RED C CAPACITOR WIRING DIAGRAM COOL, ELECTRIC HEAT, HEAT PUMP LARGE CHASSIS, 230/208V HEATERS: 2.5KW, 3.4KW, 5.
VHA18 265 Electrical Wiring Diagram 265V 60Hz 2Ø 2 WIRES FLA MCA MOP CIRCUIT BREAKER RED WHITE HEAT RELAY ELECTRONIC CONTROL (FRONT PANEL) VOLTAGE SWITCH COMP RELAY RED COMPRESSOR CONTACTOR COMPRESSOR S HARNESS COMP L1 RM HE FUSE BLACK WHITE QUICK DISCONNECT FUSE BLACK WHITE BLUE C FUSE BLOCK FUSE RED A BLACK A R BLACK BUILDING GROUND TRANSFORMER BLACK BLACK A VOLTAGE SELECTION SWITCH SET VOLTAGE TO 230V SERVICE DISPLAY AMBIENT AIR SENSOR ELECTRONIC CONTROL (REAR VIEW
VHA24 208-230 Electrical Wiring Diagram (2.5kW/3.4kW/5.0kW) 230V 60Hz 2Ø 2 WIRES FLA MCA MOP QUICK DISCONNECT COMPRESSOR S WHITE CIRCUIT BREAKER C R HE M RED RED C BLACK WHITE WHITE WIRING DIAGRAM COOL, ELECTRIC HEAT, HEAT PUMP LARGE CHASSIS, 230V HEATER: 2.5KW, 3.4KW, 5.0KW ORANGE ORANGE WASHER RED BLUE BLACK COIL SOLENOID BLACK NUT OUTDOOR FAN MOTOR 92160511 PART NO.
VHA24 265 Electrical Wiring Diagram (2.5kW/3.4kW/5.0kW) 265V 60Hz 2Ø 2 WIRES FLA MCA MOP S COMPRESSOR HARNESS COMP CIRCUIT BREAKER R HE M RED C RELAY ORANGE ORANGE BLACK WHITE WHITE WIRING DIAGRAM COOL, ELECTRIC HEAT, HEAT PUMP LARGE CHASSIS, 265V HEATER: 2.5KW, 3.4 KW, 5.0KW BLACK WASHER RED BLUE BLACK COIL SOLENOID BLACK NUT OUTDOOR FAN MOTOR 92160513 PART NO.
VHA24 208-230 Electrical Wiring Diagram (7.5/10.0kW) BUILDING GROUND 230V 60Hz 2Ø 2 WIRES FLA MCA MOP QUICK DISCONNECT WHITE WHITE WHITE COMPRESSOR S CIRCUIT BREAKER C CAPACITOR R HE M ORANGE ORANGE RED WHITE WHITE BLACK WASHER RED BLUE BLACK COIL SOLENOID BLACK NUT OUTDOOR FAN MOTOR 92160512 PART NO. PRESSURE SWITCH INDOOR BLOWER MOTOR TO BLOWER FRONT GREEN BLOWER MOTOR CONTROLLER GREEN TO MOTOR MOUNT TERMINAL DETAIL TEMINAL COVER GASKET HEATER 7.5KW, 10.
VHA24 265 Electrical Wiring Diagram (7.5/10.0kW) 265V 60Hz 2Ø 2 WIRES FLA MCA MOP WHITE WHITE S COMPRESSOR HARNESS COMP CIRCUIT BREAKER R HE M RED RED C RELAY ORANGE ORANGE RELAY RED RED WASHER RED BLUE BLACK COIL SOLENOID BLACK NUT OUTDOOR FAN MOTOR 92160514 PART NO. PRESSURE SWITCH INDOOR BLOWER MOTOR TO BLOWER FRONT GREEN BLOWER MOTOR CONTROLLER GREEN TO MOTOR MOUNT TERMINAL DETAIL TEMINAL COVER BLACK GASKET HEATER 7.5KW, 10.
Final Checklist FinalInstallation Installation Checklist Chassis Operation Chassis Operation Fresh Air Door Cooling Operation The fresh air door is an “intake” system. It is opened via a slide mechanism on the front of the The chassis set point must be at least 3°F below room located just above the indoor coil. Move temperature to ensure compressor operation. the slide left to open and right to close the door.
Service & Warranty Servicing / Chassis Quick Change Outs The chassis is designed for quick disconnect and change out. For minor electrical service, the control box cover lifts straight up after the screws and disconnect pull-out are removed. For major electrical,refrigeration, and fan service the chassis should be removed from the utility closet. Electrical Shock Hazard Pull out electrical disconnect on front of the chassis and turn off all power to unit before servicing.
Diagnostic Error Codes Unit Control Panel The display has four (4) digits. The left two digits indicate the error code (1-24) and the “On/Off” icons above these digits indicate the current state of the error code. The right two digits show the history count (up to 99) of the associated error. The display contains a maintenance icon (wrench) that will illuminate when the unit requires maintenance.
Friedrich Air Conditioning Company 10001 Reunion Place, Suite 500 San Antonio, Tx 78216 800.541.6645 www.friedrich.com VERT-I-PAK® A SERIES SINGLE PACKAGE VERTICAL AIR CONDITIONERS LIMITED WARRANTY SAVE THIS CERTIFICATE. It gives you specific rights. You may also have other rights which may vary from state to state and province to province. In the event that your unit needs servicing, contact your nearest authorized service center.
THIS PAGE INTENTIONALLY LEFT BLANK.