Accessory VPASA1 Manual (2020)

VPASA1 KIT
Pg 1/16
95303000_02
Friedrich Air Conditioning Co.
10001 Reunion Place Suite 500/ San Antonio, Texas 78216
(210) 546-0500 / (800) 541-6645 / www.friedrich.com
Installation Instructions
Sleeve Adapter Kit
For use with Vert-I-Pak® Small Chassis Series Air Conditioner and First Company® SPU Series
Wall Sleeve
NOTE: The following installation instructions apply to the Friedrich VPASA1 Sleeve Adapter Kit. This kit is designed to
adapt the VEA09, VEA12, VEA18, VHA09, and VHA12 Vert-I-Pak® Single Package Vertical Air Conditioner chassis
into an existing First Company SPU and SPX Series wall sleeve only.
There are no provisions for adapting supply ductwork, electrical connections, or condensate drain lines.
These items remain the responsibility of the equipment owner.
STOP!
Critical Closet Enclosure Dimensions Apply! (See Figure 1)
Please read entire instruction manual before proceeding!
The following clearance dimensions are required to allow replacement Vert-I-Pak chassis and adapter to fit
into the existing closet enclosure:
1) The closet width must have a minimum clearance of 4 ¼ ” on either side of the existing sleeve.
(See Figure 1A)
2) The closet depth must have a minimum of 27” from the existing sleeve edge to the front of the
closet. (See Figure 1A)
3) The closet/doorway opening must be a minimum of 27”. (See Figure 1A)
4) There must be a minimum of 6” from the bottom of the sleeve tray to the closet floor. (See Figure
1B)
STEP 1: Verify Closet and Doorway Dimensions!
Important! Verify that closet meets minimum clearance requirements prior to proceeding with
installation. (See Step 1 below and Figure 1)