Important! Your adapter will work only if existing wall sleeve is installed with a ½ bubble slope towards
the outside to accommodate for proper condensate flow.
STEP 4: Remove Existing First Company® Unit
STEP 5: Prepare Existing Sleeve
Check pitch of sleeve. Must be pitched at least 1/2 bubble (.35”/ft) to outside. (Figure 3)
Remove existing baffle. Remove screws and detach from supporting flanges. Cut sealant.
Cut edge of sleeve gusset flush or below gasket line using reciprocating saw. (Figure 4)
Tip: Angle blade to ensure gasket remains intact and without damage.
Clean existing sleeve and gaskets. Do not use solvent, instead use warm soapy water.
Measure sleeve depth. It should measure 9, 13, 16 or 21 inches deep.
Detach all supply ductwork, electrical connections, and drain connections from First Company Unit
Remove unit
Note: Refer to First Company® Installation Manual for detailed information on removal of First
Company Unit