STEP 3: INSTALL DRAIN PAN
Ensure that the drain pan is not inserted beyond 1.5 inches into the sleeve. The trough should NOT be ush with
the 3/4" ange at the base of the plenum. Attach the drain pan to the closet oor with the appropriate eld sup-
plied hardware.
IMPORTANT - To prevent water leaks use only the factory supplied mounting holes. NEVER make penetrations
in the drain pan itself.
STEP 4: INSTALL DRAIN PLUG
The drain pan comes with both left and right-hand drain connection locations. Determine which of the two
connections will be used to drain the condensate. Then, with the factory supplied drain plug, plug the unused
opening.