Service and Parts Manual (2019, 2020, 2021, 2022)
121 PB
COMPONENTS TESTING
Test System Flow
Cooling mode 
The pressure is high. 
Test system 
pressure. Is the 
pressure normal at the 
low service port ?
The pressure is low. 
Air remaining at the 
yes
refrigerant system.
Recharge refrigerant 
after air purging with 
the vacuum 
pump. Is the low 
pressure normal?
NO
Recharge 
yes
refrigerant . 
The system needs 
refrigerant. 
Recharge  refigerant. 
Did the low  pressure rise ? 
The refrigerant system 
blocked. Please check 
the Capillary Tube (or 
electronic expansion 
valve) for blockage?
Check check valve and 4-
way valve.
Is the pressure is 
close to static 
NO
pressure? 
NO
Unsolder the capillary tube 
ASS'Y(or electronic expansion 
valve). Clear the capillary tube 
with compessed nitrogen.
yes
NO
yes
Heating mode 
4-way valve clogged or
compressor exhaust blocked.
The pressure is high. 
Test system 
pressure. Is the pressure
 normal at the high
 pressure service port?? 
The pressure is low. 
Air remaining at the 
yes
refrigerant system.
Recharge refrigerant 
after air purging with 
the vacuum 
pump. Is the high 
pressure normal? 
NO
yes
Recharge refrigerant  
The system needs 
refrigerant. Add refrigerant.
Is the pressure normal. 
Is the pressure close 
to static pressure? 
yes
4-way valve clogged or 
compressor exhaust blocked.
NO
Check heat exchanger and 
4-way valve.
NO
Remove the back 
panel."see"the 
capillary tube1 and 
defrosting?
yes
capillary tube2. Are 
they 
NO
The capillary tube  
blocked. Unsolder the 
capillary tube ASS'Y. Blow out 
capillary tube1 and capillary 
tube2 with compressed 
nitrogen
 . 