Service and Parts Manual (2019, 2020, 2021, 2022)
65 PB
OPERATION
Control Logic Description
(1) Outdoor  fan and  compressor  stop.
(2) Temperature  setting function  is disabled,  and  no setting  temperature  is displayed.
(3) Indoor  fan can be  set to high/medium/low, but can  not be  set to auto.
Cooling Mode
Indoor fan running rules:
In cooling  mode,  indoor  fan  runs all the time  and  the  speed  can be  selected  as high,(medium),  
low and  auto.
The  auto  fan:
T1  is indoor  room temperature. Ts  is  setting temperature. 
Outdoor fan running rules:  
Once the outdoor fan start up, it will follow the below rules:  
Single outdoor fan: First, it will run in an invariable speed for a short time; Then it will regulate the  
speed by the outdoor-coil temperature. 
Double outdoor fan: If it has two outdoor fans, the upper fan regulates the speed by the rules,  
and the downer fan speed lower than the upper fan speed for 30rpm~60rpm.  
T
1-
Ts
0 
2
Inverter outdoor unit: 
Compressor  and  outdoor  fan running rules: 
Once the  compressor  starts up, it will follow the below  rules: 
When  indoor  room  temp.T1  is lower than Ts, the compressor  and  outdoor  fan  will shut off. 
When  T1  is higher than Ts+1,  the compressor  and  outdoor  fan  will start up. 
4
Low 
Medium 
High 
-1