Service and Parts Manual (2019, 2020, 2021, 2022)
67 PB
OPERATION
Control Logic Description
ΔT=T1 - T s 
Runni ng mode  
 Auto  Mode
This mode can be chosen with remote controller and the setting  temperature can be changed 
between 61°F~86°F(16°C~30) . 
In auto mode, the  unit will choose cooling, heating or fan -only mode according to  ΔT ( ΔT 
=T1 -Ts). 
Cooling 
ΔT>3 7°F(3°C)
27°F(-3 ) ≤ ΔT≤ 37°F(3°C)
Fan-only 
ΔT  <27°F(-3°C)
Heating  
Indoor fan will run at auto fan of the relevant mode. The louver operates same as in relevant
mode. If the compressor keeps  stopping for 10 minutes or the setting temperature is modified , 
the machine will choose mode according to ΔT again.
 Evaporator Low -tem perature Protection
DC -Inverter
AC  will enter  T 2 protection if  any  of  the following condition  is satisfied.
Condition:
TE6
T2
On
Off
TE5
Cooling  mode :  When  the  indoor  coil  tem p.  T2   keeps  lower  than  TE5  for  120 seconds , 
the  compressor  and  outdoor  fan  will  shut   of f.  When   T2   is  higher  than TE6 ,  the 
compressor and outdoor fan will restart.