Service and Parts Manual (2019, 2020, 2021, 2022)
68 PB
OPERATION
Control Logic Description
T3
TE1 0
On
Off
TE1 1
Condition1: 
Cooling  mode:  When  the outdoor  coil temp. T3  keeps  higher than T2  for 10 seconds, the  
compressor  and  outdoor  fan  will  shut  off.  When  T3  is  lower  than  T1,  the compressor  
and  outdoor  fan  will restart up. 
Condition2: 
Heatin g mode:  Wh en  the  indoor  coil temp. T3  keeps  higher than T2     for 10 seconds, the 
compressor   and   outdoor   fan  will  shut  off.  When   T3   is  lower  than  T1,   the compressor 
and outdoor  fan  will restart up. 
 Condenser  High-tem perature  Protection  
DC -Inverter outdoor  unit
AC  will enter T3 protection if  any  of  the  following conditions  is satisfied.