Field Settings (Indoor Unit Parameter Revision)
PARAMETER  
C O DE  
PARAMETER  
DE SC RIPTIO N 
NO TE 
PARAMETER  VALUE &RE PRE SE NTATIO N 
DAT A 
TY PE 
RE PRE SE NTATIO N 
(FUNC TIO N C O D E ) 
1 
Integer 
Self Recovery of 
Power Break 
2  Integer Temperature Type 
0:Cancel Self Recovery of Power 
Break function ; 
1:Self Recovery of Power Break ;
others:invalid 
3 
Integer 
Temperature Display 
Type   
0:Centigrade Temperature ; 
1:Fahrenheit Temperature ; 
others:invalid 
4 
0:Default display set temperature ; 
1:Default display room temperature ; 
others:invalid 
Integer 
Ratio of ambient 
temperature sensed 
by indoor 
temperature 
sensor(cooling 
mode) 
0~10valid ,more than 10 default is10 
0:0% ;1:10% ;… ;10:100% 
5 
Filter Clean 
Indication 
Integer 
0-entirely use
temperature
sensed b y wired
remote  controller;
10- entirely use
temperature
sensed b y indoor
unit
6  Integer Filter Clean Time Set 
0:Cancel Filter Clean prompt function ; 
1:Set Filter Clean prompt function ;
others:invalid 
7 
0~32 ,more than 32 default is 32*1000h 
Integer 
Installation Height 
Compensation 
8 
Integer 
0~10m ,more than 10m default is 10. 
=0,1,2 :no fan speed compensation; 
=3: increase fan speed;   
=4~10: increase more fan speed. 
Cooling Temperature 
Compensation 
(indoor unit 
temperature sensor ) 
9 
Integer 
0:0°C ;  1: -0.5 °C;2: -1°C
3:-1.5 ºC; 4: -2ºC; 5: -2.5ºC;
Heating Temperature 
Compensation
(indoor unit 
temperature sensor ) 
10  Integer Static Pressure Set 
0:0°C;1:-0.5 °C;2:-1°C
3:-1.5 °C 4: -2°C;5:-2.5 °C;
6:-3°C;7:-3.5 °C; 8: -4°C; 9: -4.5°C
10:-5°C  ( the wired controller displays 
intege r with the symbol )
Duct type (DC 
motor ) 
12  Integer 
1~240 ,function code=static pressure   
more than the limit static pressure 
default the limit  static pressure ,Default 
is 0( default static pressure,  related to 
models ) 
Ratio of temperature 
sensed by indoor 
temperature 
sensor( (Heating 
mode) 
0~10valid ,more than 10 default is10 
0:0% ;1:10% ;… ;10:100% 
13 
Charac
0-entirely use
temperature
sensed b y wired
remote  controller;
10-entirely use
temperature
sensed b y indoor
unit
ter 
Temperature 
Adjustment-Cooling 
-10~10  (Sing le Ch aracter with
symbol )
14 
Temperature 
displayed on wired 
controller 
Charac
ter 
Temperature 
Adjustment-Heating 
-10~10  (Sing le Ch aracter with
symbol )
25 
Temperature 
displayed on wired 
controller 
Integer 
Access control, fire 
protection, ON/OFF 
function set 
=0 ,Access control, fire 
  protection functions are all invalid ; 
=1 ,Access control function is valid ; 
=2 ,fire protection function is valid ; 
=3 ,Access control, fire protection are 
all valid;   
=4 ,ON/OFF function are all valid.  
6 : -3ºC; 7: -3.5ºC; 8: -4°C; 9: -4.5°C
10: -5°C (The wired controller displays 
integer with the symbol.)