Brochure

27 | FLOATING AIR
®
SERIES DUCTLESS
PR0 SERIES | SPECIFICATIONS
PERFORMANCE RATINGS Multi Zone - The Insider
®
Concealed Ducted Heat Pumps
9k 12k 18k 24k
INDOOR MODEL FPHFD09A3A FPHFD12A3A FPHFD18A3A FPHFD24A3A
SPECIFICATIONS
CAPACITY COOLING (RATED) Btu 9000 12000 18000 24000
CAPACITY HEATING (RATED) Btu 9000 12000 18000 24000
MOISTURE REMOVAL Pts/h 2.0 3.0 5.0 5.1
AIRFLOW CFM 235/285/309 235/285/338 370/440/529 501/574/647
SOUND RATING (MAX.-MIN.) dB-A 29/27/26 36/33/30 38/35/33 38/36/34
ELECTRICAL DATA
POWER SOURCE V-Hz-Phase 230/208-60-1 230/208-60-1 230/208-60-1 230/208-60-1
POWER AND COMMUNICATION CABLE No. x AWG 4 x 14AWG 4 x 14AWG 4 x 14AWG 4 x 14AWG
REFRIGERATION SYSTEM
CONNECTIONS Flare Flare Flare Flare
LIQUID LINE O.D. in 1/4 1/4 1/4 3/8
SUCTION LINE O.D. in 3/8 3/8 1/2 5/8
DIMENSIONS & WEIGHT
W X H X D in 35 7/8 x 7 1/2 x 17 5/8
48 7/16 x 7 1/2 x 17 5/8 39 x 10 5/8 x 30
NET WEIGHT lbs 39.7 39.7 49.6 70.5
SHIPPING WEIGHT lbs 46.3 47.4 56.2 81.6
Your operating costs will depend on your utility rates and use. The estimated operating cost is based on a electricity cost of $ .12 per kWh.
For more information, visit www.ftc.gov/energy.
Due to continuing research in new energy-saving technology, specications are subject to change without notice.
PERFORMANCE RATINGS Multi Outdoor
18k
24k 36k 42K
OUTDOOR MODEL
FPHMR18A3A
FPHMR24A3A FPHMR36A3A
FPHMR42A3A
SPECIFICATIONS
POWER SOURCE
208~230/60/1 208~230/60/1 208~230/60/1 208~230/60/1
EST. YEARLY OPERATING COST
$ $90 $172 $259 $277
RUNNING CURRENT COOLING RATED
A
6.5
8.7 11
17.5
RUNNING CURRENT HEATING RATED
A
7.3
8.7 13
17
POWER INPUT COOLING MIN. RATED MAX.
W 1440 (510
~
2610) 1920 (420
~
2640)
2520 (700~5000)
4020 (700~5000)
POWER INPUT HEATING MIN. RATED MAX.
W 1530 (450
~
3510) 1920 (420
~
4020)
3060 (600~6000)
3870 (600~6000)
POWER AND COMMUNICATION CABLE
No. x AWG
4 x 14AWG 4 x 14AWG 4 x 14AWG 4 x 14AWG
DIMENSIONS W x H x D
in
33
7
/8 x 26
3
/8 x 12
1
/4 37
3
/8 x 33 x 13
3
/8
37
3
/8 x 41
3
/8 x 13
3
/8 37
3
/8 x 41
3
/8 x 13
3
/8
NET WEIGHT
lbs 108 159 186 196
SHIPPING WEIGHT
lbs 119 170 216 225
REFRIGERATION SYSTEM
REFRIGERANT
R410A R410A R410A R410A
FACTORY PRECHARGE
oz
63 81 106 120
FACTORY PRECHARGE
ft
50
75 100
125
LIQUID LINE O.D.
in
1
/4
1
/4
1
/4
1
/4
SUCTION LINE O.D.
in
3
/8
3
/8
3
/8
3
/8
MIN./MAX. LINE LENGTH (EACH)
ft
25/82
25/66 25/66
25/66
LINE LENGTH (TOTAL)
ft
164
197 197
262
MAX. HEIGHT DIFFERENCE
ft
49
49 49
49
SOUND PRESSURE LEVEL COOLING
dB
55
59 59
59
SOUND PRESSURE LEVEL HEATING
A
55
59 59
59
OPERATING RANGE COOLING
°F DB
14
~
115
14~115 14~115 14~115
OPERATING RANGE HEATING
°F WB -13~75 -13~75 -13~75
4-75
MINIMUM AMPACITY
A
21A
25A 32A 35A
MAX. TD FUSE/ BREAKER
A
30A
30A 50A 50A