Sleeve Installation Guide

INSTALLATION INSTRUCTIONS
FOR "W
SE" SLEEVE
MOUNTING HARDWARE PROVIDED
ITEM
DESCRIPTION
NO.
QTY.
1
SCREW, #12A X 2"
5
WALL PREPARATION:
STEP 1
The wall opening required for a "WSE" SLEEVE is 17 1/4" high by 27 1/4" wide.
STEP 2
LINTELS must be used in opening of brick veneer and masonry walls to support the material above the "WSE" SLEEVE.
The following considerations should also be given:
A. Adjustable SUB-BASE SB89 or other unit support must be provided for panel wall type construction
and for walls less than 8" thick.
B. A minimum distance of 1" must be allowed on all sides of the unit to adjacent wall and floor. Where the
subbase is required, the minimum distance from the floor to the sleeve must be 3 1/2". To minimize
chances of short cycling of the compressor, the minimum clearance between the ceiling and the top of
the unit should be 24". (See Figure 1).
FIGURE 1
Side View
INSIDE
WALL
7/8" MINIMUM BEYOND
INSIDE WALL
WSE SLEEVE
LINTELS
5" (127 mm)
5" (127 mm)
WALL MOUNT
SCREW LOCATIONS
DRAIN
EXTENSION
9/16" MINIMUM
BEYOND OUTSIDE WALL
OUTSIDE WALL
24" MINIMUM REQUIRED
FROM TOP OF UNIT TO CEILING
1" MINIMUM
3 1/2" FOR SUBBASE
5 1/2" MAXIMUM FOR SUBBASE
MINIMUM SPACING REQUIRED
ON ALL SIDES OF UNIT