Installation guide

Electrical connection (non=Canada) - 3 wire cord
3-wire receptacle
(NEMA type 10-30R)
could result in personal injury or even death.
1 Turn off power supply to outlet.
2 Remove the screw securing the terminal block
access cover on the back of the dryer.
3 Install a UL-approved strain relief according to the
power cord/strain relief manufacturer's instructions
in the power cord entry hole below the access
panel. At this time, the strain relief should be
loosely in place.
4 Thread an UNPLUGGED,UL-approved, 30 amp.
power cord, NEMA i0-30 type SRDT,through the
strain reliefi
S Attach the power cord neutral (center wire)
conductor to the SILVER colored center terminal on
the terminal block. Tighten the screw securely.
6 Attach the remaining two power cord outer
conductors to the outer, BRASScolored terminals on
the terminal block. Tighten both screws securely.
ELECTRICAL SHOCK HAZARD
Do not make a sharp bend or crimp wiring/conductor
at connections.
7 Follow manufacturer's guidelines for firmly securing
the strain relief and power cord.
8 Reinstall the terminal block cover.
/
DO NOT remove
internal ground in a
3-wire system[
Neutral
/J terminal