Installation Instructions

7
36" GAS RANGE INSTALLATION INSTRUCTIONS
2
Electrical Requirements
1
Cabinet Construction
To eliminate the risk of burns or re by
reaching over heated surface units, do not have cabinet
storage space above the range. If there is cabinet storage
space above range, reduce risk by installing a range
hood that projects horizontally a minimum of 5" (12.7 cm)
beyond the bottom of the cabinet.
1.1
Installation: Cabinet on Both Sides
1. If range will be installed with a cabinet on both sides,
Draw a center line on the oor between the cabinets
(Figure 3).
2. If back of range will not be ush with the wall (the
location of the outlet may not allow the range to be
positioned against the wall), draw a line on the oor
where the back edge of the range will be.
3. Install anti-tip brackets (see "Anti-Tip Bracket
Installation").
1.2
Installation: Cabinet on One Side Only
1. If range will be installed with a cabinet on one side
only, move the range into nal position.
2. Draw a line on the oor along the side of the range
that is not against the cabinet. If back of range will
not be ush with the wall (the location of the outlet
may not allow the range to be positioned against the
wall), draw a line on the oor where the back edge of
the range will be.
3. Install anti-tip brackets (see "Anti-Tip Bracket
Installation").
1.3
Installation: Without Cabinet
1. If range will not be installed against a cabinet, move
range into nal position.
2. Mark on the oor along both sides of the range.
If back of range will not be ush with the wall (the
location of the outlet may not allow the range to be
positioned against the wall), draw a line on the oor
where the back edge of the range will be.
3. Install anti-tip brackets (see "Anti-Tip Bracket
Installation").
Follow instructions for
the type of installation you have
Center
Line of
Range
Figure 3: Cabinet construction
Grounding Requirements
This appliance must be installed and grounded by a
qualied technician.
In the United States, install in accordance with the National
Fuel Gas Code ANSI Z223.1/NPFA No. 54, latest edition
and National Electrical Code NFPA No. 70 latest edition,
and local electrical code requirements. In Canada, install in
accordance with CAN/CGA B149.1 and CAN/CGA B149.2
and CSA Standard C22.1, Canadian Electrical code, Part
1-latest editions and local electrical code requirements.
This appliance requires a dedicated, properly grounded and
polarized branch circuit protected by a 15 amp GFI (ground
fault interrupter) circuit breaker or time delay fuse. See
serial plate for proper voltage.
For personal safety, this appliance must be properly
grounded. For maximum safety, the power cord must
be plugged into an electrical outlet that is the correct
voltage, is correctly polarized and properly grounded
in accordance with local codes. It is the personal
responsibility of the consumer to have the appropriate
outlet with the correct, properly grounded wall receptacle
installed by a qualied electrician.
Be sure the wall receptacle is within reach of the
appliance's nal installed location.
Do not pinch the power supply cord between the range
and the wall.
Electrical Shock Hazard –Electrical ground is
required on this appliance. Use only the power cord
supplied with the appliance. Improper connections and
grounding may result in electric shock, damage to the
appliance, personal injury, re or death.
Figure 4: 3-Prong Gounded Electrical Outlet